Mitsubishi FR - S500 instruction manual 14.4 E2PROM write selection, 132

Page 141

<Setting>

n10

 

Operation Mode

Mode at Power-On or at Power Restoration

Setting

Pr. 79

after Instantaneous Power Failure

 

 

0

PU or external operation

Placed in the external operation mode.

 

1

PU operation

Placed in the PU operation mode.

 

2

External operation

Placed in the external operation mode.

 

 

External/PU combined

The running frequency is given in the PU

 

3

operation mode and the start signal in the

 

operation mode

 

 

external operation mode.

 

 

 

 

 

External/PU combined

The running frequency is given in the external

 

4

operation mode and the start signal in the PU

 

operation mode

0

 

operation mode.

 

 

(Factory

 

 

MRS signal ON .....Can be switched to PU

setting)

 

 

operation mode.

 

7

External operation mode

(Output stop during

 

external operation)

 

 

 

 

 

 

MRS signal OFF ...Switching to PU operation

 

 

 

mode inhibited.

 

 

 

X16 signal ON .......Switched to external

 

8

External/PU combined

operation mode.

 

operation mode

X16 signal OFF .....Switched to PU operation

 

 

 

 

 

mode.

 

0

Computer link operation

Disabled when PU is selected. Enabled when

 

external is selected.

 

 

 

 

1

PU operation only

Disabled

 

2

Computer link operation

Enabled

 

3

External/PU combined

Disabled

 

operation

1

 

 

4

External/PU combined

Disabled

 

 

operation

 

 

 

 

7

External operation (PU

Enabled only for external operation when the

 

operation interlock)

PU interlock signal (MRS) is ON.

 

 

 

8

PU or external (signal

Enabled only for external operation (X16: ON).

 

switching)

 

 

 

n10 can be changed independently of the operation mode of the operation panel.

Setting of n10 = "1" is made valid when "0" or "2" is set in Pr. 79 "operation mode selection".

Refer to to (page 118)

2.14.4 E2PROM write selection

You can choose whether the parameters are stored into E2PROM or not at the parameter setting for computer communication.

Parameter

Name

Factory

Setting

Remarks

Setting

Range

 

 

 

 

E2PROM write

 

 

0: Written to RAM and E2PROM

n12 (342)

0

0, 1

1: Written to RAM only

selection

Not written to E2PROM*

 

 

 

 

Setting is enabled when Pr. 30 = "1"

The parameter number in parentheses is the one for use of the parameter unit (FR-PU04). * When reset is performed, the parameter value will be the value of E2PROM.

132

Image 141
Contents SR5 0 This section is specifically about safety matters Conditions, resulting in death or severe injuryCause physical damage only Page Page Page Multi-speed setting RL, RM, RH, REX signals Setting 0, 1, 2 How to Use the Input SignalsBiases and gains of the frequency setting voltage current Handling of the RS-485 ConnectorStall prevention Frequency jumpOperation mode selection PID control 101 Restart settingMonitoring reference Retry function PWM carrier frequency Applied motor137 To know the operating status at the occurrence of alarm145 Correspondence between digital and actual characters 145Abbreviations WiringTerminal connection diagram Japanese VersionFR-S520-0.1K to 3.7K -R -C FR-S540-0.4K to 3.7K -R Layout and wiring of main circuit terminals FR-S520S-0.1K to 1.5K -R -C FR-S510W-0.1K to 0.75K -RNFB MC North America Version InverterFR-S520-0.1K to 3.7K-NA FR-S540-0.4K to 3.7K-NA R FR-S510W-0.1K, 0.2K, 0.4K-NA FR-S510W-0.75K-NA Reduce the output current FR-S540-0.4K to 3.7K-ECR European VersionFR-S520S-0.2K to 1.5K-EC R FR-S540-0.4K, 0.75K, 1.5K, 2.2K, 3.7K-EC RFR-S520S-0.2K, 0.4K, 0.75K-EC R FR-S520S-1.5K-EC R Main circuit Description of I/O Terminal SpecificationsControl circuit Terminal names in parentheses are those of the EC versionRUN Cables, wiring lengths, crimping terminals, etc How to Use the Main Circuit TerminalsFR-S520S-0.1K to 1.5K -R FR-S520S-0.2K to 1.5K-EC R FR-S510W-0.1K to 0.75K -R FR-S510W-0.1K to 0.75K-NAWiring instructions Selection of peripheral devices Peripheral devicesAC Reactor DC Reactor Model L1, NCables mm2 Line-to-line leakage currents To-ground leakage currentsType SP, CF, SF, CP During commercial powerRated sensitivity current ∆ n ≥ 10 ⋅ lg1+Ign+lg2+lgmInverters primary side magnetic contactor MC Power-off and magnetic contactor MCOFF STF STRNFB FR-BAL Regarding noise and the installation of a noise filterNoise reduction examples Grounding precautionsBLF BIFJapanese power harmonic suppression guideline Regarding power harmonicsReceived Power Voltage 5th 7th 11th 13th 17th 19th 23rd Over Conversion Factors for FR-S500 Series Harmonic suppression techniques Harmonic suppression technique requirementRated 6kV No reactor, 100% operation ratioHow to Use the Control Circuit Terminals Terminal block layoutM3 A, B, C terminals Al 0.5-6WH Input signals are set to sink Using tweezers, a pair of longChanging the control logic RUN 24VDC STRSTR R Right The forward/reverse rotation signal is Input TerminalsRun start and stop STF, STR, Stop Three-wire type connection STF, STR, Stop STR-SD STF-SDBasic Voltage input 10, 2External frequency selection REX, RH, RM, RL Manual-Automatic SwitchingCurrent input 4, 5, AU AU-SD on OFFREX External commandJapanese version FM Indicator connection and adjustmentOutput waveform of terminal FM CPU NA and EC version AMControl circuit common terminals SD, 5, SE Signal inputs by contactless switchesSecond function selection RT signal Setting Current input selection AU signal SettingStart self-holding selection Stop signal Setting External thermal relay input Setting Output shut-off MRS signal SettingJog operation JOG signal Setting Reset signal SettingJog operation using external signals PU operation/external operation switching Setting PID control valid terminal SettingWhen connecting the parameter unit Use the optional FR-CB2System configuration examples RS-485 communication4P Twisted pair cable, 4 pairs Wiring of one RS-485 computer and one inverter Wiring methodsMC1 Design InformationCommunication Parameters Only for the Type FunctionsFunction Parameter List Func- Pa- Indica- tion rame- tion ter Minimum Factory Cus Name Setting RangeMinimum Factory Refer Cus Name Setting Range FM AM THM, THT, GF OHT, OLT, PE, OPTPWM Selection functions PID ECL Alarm history 115 ClearFunc Tion CationNA, EC Com Minimum For details of the program, refer to page 118 onwardsList of Parameters Classified by Purpose of Use Related to monitoring Name Factory Setting Remarks SettingExplanation of Functions Parameters Torque boostParameter Name Factory Setting Setting Range EC version Maximum and minimum frequencyBase frequency, Base frequency voltage EC version Remarks Range Multi-speed operation to toAcceleration/deceleration time Frequency setting Hz 120 Acceleration Deceleration time s Electronic overcurrent protection DC injection brakeOperation, etc. or the timing of operating Name Factory Starting frequencyLoad pattern selection Jog frequency Name Factory Setting Setting Range RemarksRUN key rotation direction selection Refer to Refer to ,Stall prevention function and current limit function Stall Prevention OL Signal Operation Fast OutputCelerationDe Operation Activated Deceleration Operation Not Activated Regenerative DrivingStall prevention Where, a = 100Acceleration/deceleration pattern Set the acceleration/deceleration patternFunction Description Frequency jump Extended function display selectionSpeed display Setting Biases and gains of the frequency setting voltage currentName Factory Setting Use Pr , calibration parameter C4 forFlicker ... Parameter setting complete How to change the highest frequencyOperationDisplay Set value HzPress the SET key to set the value Voltage gain appears Press the SET key to show the analogTurn the setting dial to read another parameter Key to return toKey twice to show the next parameter Start-time ground fault detection selection Output Terminal Function ParametersUp-to-frequency sensitivity Output frequency detection Current Detection Function Parameters Parameter Name Factory Setting Remarks RangeOutput current detection functions On OFFZero current detection Display Function Parameters Monitor displayLED Setting dial function selection Press the RUN key to start the inverterRefer to Restart Operation Parameters Restart settingMonitoring reference Maximum output voltage of terminal AM is 5VDCRefer to the following table and set the parameters Setting DescriptionAutomatic restart operation after StfstrOr PU digital preset frequency Remote setting function selectionOperation panel operation procedure Additional Function ParametersFrequency setting storage conditions Pr SettingFunction E 2PROM Input terminal function selection Terminal Function Selection ParametersMRS Setting Signal Functions Related Parameters NameREX JOGOutput terminal function selection Setting Signal Function Operation ParametersSame function may be set to more than one terminal Referred toOperation Selection Function Parameters Pr Setting Number of Retries Alarm Signal OutputRetry function Protective Functions Major Failures for RetriesParameter Number Setting Description PWM carrier frequencyYou can change the motor sound Voltage input selection Applied motorSet the motor used Acceleration/deceleration time, which is a slope up/down toParameter Name Factory Setting Setting Range Remarks Reset selection/PU stop selectionSetting Remarks Reset Selection PU Stop Selection SettingOperation panel Restarting method with Shown Key input fromCooling fan operation selection Parameter write inhibit selection Pr Setting FunctionReverse rotation prevention selection Operation mode selectionFunction LED Indication * PU Mode SignalEXT RUN EXTMRS PU operation interlockOperation mode switching by external signal X16 Signal Operation ModePID control to Setting Basic PID control configuration PID action overview102 Reverse action PID actionIncreases the manipulated Variable output frequency if Deviation X = set pointDeviation Wiring exampleNegative RUNFUP,FDNParameter setting O signalsName Setting Description 105106 Adjustment procedure107 Calibration exampleStart ENDSet point input calibration Detector output calibration108 Slip compensation Auxiliary Function Parameters11.2 Automatic torque boost selectionOperating conditions 110Ordinary V/F control and torque boost Pr , Pr are valid Calibration Parameters Parameter Name Factory Setting RemarksMotor primary resistance Meter frequency meter calibration Japanese version112 Flicker ... Parameter setting completeMeter frequency meter calibration NA and EC version When the FR-PU04 is used, make calibration with Pr 114 OperationDisplay Erases the alarm history Alarm history clearClear Parameters Parameter clearOperational functions Symbol Switching TypeOperation mode-based functions 14.1 Communication settingsCommunication-related parameters 118Description Setting 119CR LF Computer programming Communication protocol Operation Run RunningInverter Monitor Parame Reply data from inverter to computer during data write Data formatReply data from inverter to computer during data read 121Data definitions Signal Ascii Code DescriptionSend data from computer to inverter during data read Control codesSTX ACK ENQ 123Instruction Data 124H7F HFFPage Setting items and set data 126FF = Calibra 127HEC Nication TionError Definition Error Code List128 Description DataCommunication error Operation at alarm occurrenceGeneral flowchart Program exampleOperation and speed command write Location Selection N8 Pr Operation Command writeN9 Pr Speed Command write N8 Pr operation Command write Link start mode selectionN10 Link start mode Setting is enabled when Pr = Selection Explanation of table External14.4 E2PROM write selection Parameter unit display language switching Parameter Unit FR-PU04 SettingN13 Setting Display Language 15.2N15 PU contrast adjustment Setting is enabled when Pr = PU contrast adjustmentPU main display screen data selection N16 100PU disconnection detection/PU setting lock Monitor display and Resetstop key are validN17 Setting PU Disconnection Detection PU Setting Lock 136 FunctionsError alarm definitions Errors AlarmsMajor failures OC1 FR-PU04OC2 FR-PU04 138OC3 FR-PU04 OV1 FR-PU04OV3 139THM THTOHT FR-PU04 140OLT FR-PU04 OPT FR-PU04For only the type having the RS-485 communication function Minor failures141 PUE142 Write errors Er1 FR-PU04 Control Mode143 144 Er2 FR-PU04 PU/EXT ModeOperator ERR Er3 FR-PU04 Incr I/PResetting the inverter Correspondence between digital and actual charactersActual Display Motor remains stopped TroubleshootingMotor rotates in opposite direction Speed greatly differs from the settingAcceleration/deceleration is not smooth Motor current is largeOperation panel display is not operating Operation mode is not changed properlyParameter write cannot be performed Motor produces annoying soundPrecautions for maintenance and inspection Precautions for Maintenance and InspectionCheck items Periodic inspectionPressure test Insulation resistance test using meggerDaily and periodic inspection Interval DailyInspection Description 151Interval Daily 1 yearInspection Interval Checking the inverter and converter modules Preparation Checking methodModule device numbers and terminals to be checked Part Name Standard Replacement Interval Description Replacement of partsCooling fan Inverter Model No Fan TypeAIR Flow Relays Smoothing capacitorsTypical Measuring Points and Instruments Measurement of main circuit voltages, currents and powersPf2= Pf1=158 Measuring Point Remarks Instrument Reference Measured ValueRH, RM, RL, MRS Measuring PointRES-SD Measuring Remarks Instrument160 CationsSpecification List Phase 200V power supplyRatings Phase 400V power supply Single-phase 200V power supply Single-phase 100V power supply Common specifications NA, EC Outline Drawings 168 Parameter unit FR-PU04 Outline drawing Panel cut dimension drawing170 InstructionsPeripheral Selecting Instructions Selecting InstructionsDisuse of power factor improving capacitor power capacitor Installation of thermal relayHandling of primary side magnetic contactor Handling of secondary side magnetic contactorWiring Cable thickness and wiring distanceOperating Instructions OperationPower supply InstallationInverter-driven 400V class motor Rectifying the motor insulationSuppressing the surge voltage on the inverter side 176 AppendixData Code Computer Func- Parameter tion NumberExtension Link Data178 Data Code Computer Link Parameter ExtensionRead 179 180 181 Link Parameter Extension Setting Data Code 7F/FFData Code Computer Func Name Link Data TionPrint Date Manual Number Revision Manual number is given on the bottom left of the back cover