Mitsubishi FR - S500 Output Terminal Function Parameters, Up-to-frequency sensitivity

Page 87

2.3.19 Start-time ground fault detection selection

You can choose whether to make ground fault detection valid or invalid at a start. Ground fault detection is executed only right after the start signal is input to the inverter.

 

 

Factory

Setting

 

 

Parameter

Name

Setting

Remarks

 

Range

 

 

 

<EC version>

 

 

 

Start-time ground

 

 

0: Ground fault detection for

Setting is

 

0

 

protection is not executed.

40

fault detection

0, 1

enabled when

 

selection

<1>

 

1: Ground fault detection for

Pr. 30 = "1".

 

 

 

protection is executed.

 

 

 

 

 

CAUTION

1.If a ground fault is detected with "1" set in Pr. 40, alarm output "" is detected and the output is shut off.

2.If the motor capacity is less than 0.1kW, ground fault protection may not be provided.

REMARK

When a ground fault is detected with "1" set in Pr. 40, an approximate 20ms delay occurs at every start.

2.4 Output Terminal Function Parameters

2.4.1 Up-to-frequency sensitivity

The ON range of the up-to- frequency signal (SU) output when the output frequency reaches the running frequency can be adjusted between 0 and ±100% of the running frequency. This parameter can be used to ensure that the running frequency has been reached to provide the operation start signal etc. for related equipment.

 

 

Running

Adjustable

Output frequency (Hz)

frequency

range Pr.41

 

Time

 

 

 

Output signal

OFF

ON

OFF

(SU)

 

ON

OFF

Start signal

 

 

 

 

Parameter

Name

Factory

Setting

Remarks

Setting

Range

 

 

 

41

Up-to-frequency

10%

0 to 100%

Setting is enabled when Pr. 30 =

sensitivity

"1".

 

 

 

REMARKS

Using Pr. 64 or Pr. 65 to change terminal assignment may affect the other functions. Make setting after confirming the function of each terminal. (Refer to page 90.)

Related parameters

Assignment of SU signal to terminal Pr. 64 "RUN terminal function selection", Pr. 65 "A, B, C terminal function selection" (refer to page 90)

78

Image 87
Contents SR5 0 This section is specifically about safety matters Conditions, resulting in death or severe injuryCause physical damage only Page Page Page Multi-speed setting RL, RM, RH, REX signals Setting 0, 1, 2 How to Use the Input SignalsFrequency jump Handling of the RS-485 ConnectorBiases and gains of the frequency setting voltage current Stall preventionRetry function PWM carrier frequency Applied motor Restart settingOperation mode selection PID control 101 Monitoring referenceCorrespondence between digital and actual characters 145 To know the operating status at the occurrence of alarm137 145Abbreviations WiringTerminal connection diagram Japanese VersionFR-S520-0.1K to 3.7K -R -C FR-S540-0.4K to 3.7K -R Layout and wiring of main circuit terminals FR-S520S-0.1K to 1.5K -R -C FR-S510W-0.1K to 0.75K -RNFB MC North America Version InverterFR-S520-0.1K to 3.7K-NA FR-S540-0.4K to 3.7K-NA R FR-S510W-0.1K, 0.2K, 0.4K-NA FR-S510W-0.75K-NA Reduce the output current FR-S540-0.4K to 3.7K-ECR European VersionFR-S520S-0.2K to 1.5K-EC R FR-S540-0.4K, 0.75K, 1.5K, 2.2K, 3.7K-EC RFR-S520S-0.2K, 0.4K, 0.75K-EC R FR-S520S-1.5K-EC R Terminal names in parentheses are those of the EC version Description of I/O Terminal SpecificationsMain circuit Control circuitRUN FR-S510W-0.1K to 0.75K -R FR-S510W-0.1K to 0.75K-NA How to Use the Main Circuit TerminalsCables, wiring lengths, crimping terminals, etc FR-S520S-0.1K to 1.5K -R FR-S520S-0.2K to 1.5K-EC RWiring instructions Selection of peripheral devices Peripheral devicesAC Reactor DC Reactor Model L1, NCables mm2 Line-to-line leakage currents To-ground leakage currents∆ n ≥ 10 ⋅ lg1+Ign+lg2+lgm During commercial powerType SP, CF, SF, CP Rated sensitivity currentSTF STR Power-off and magnetic contactor MCInverters primary side magnetic contactor MC OFFNFB FR-BAL Regarding noise and the installation of a noise filterBIF Grounding precautionsNoise reduction examples BLFJapanese power harmonic suppression guideline Regarding power harmonicsReceived Power Voltage 5th 7th 11th 13th 17th 19th 23rd Over Conversion Factors for FR-S500 Series No reactor, 100% operation ratio Harmonic suppression technique requirementHarmonic suppression techniques Rated 6kVHow to Use the Control Circuit Terminals Terminal block layoutM3 A, B, C terminals Al 0.5-6WH Input signals are set to sink Using tweezers, a pair of longChanging the control logic RUN 24VDC STRSTR R Right The forward/reverse rotation signal is Input TerminalsRun start and stop STF, STR, Stop Three-wire type connection STF, STR, Stop STR-SD STF-SDBasic Voltage input 10, 2AU-SD on OFF Manual-Automatic SwitchingExternal frequency selection REX, RH, RM, RL Current input 4, 5, AUREX External commandJapanese version FM Indicator connection and adjustmentOutput waveform of terminal FM CPU NA and EC version AMControl circuit common terminals SD, 5, SE Signal inputs by contactless switchesSecond function selection RT signal Setting Current input selection AU signal SettingStart self-holding selection Stop signal Setting External thermal relay input Setting Output shut-off MRS signal SettingJog operation JOG signal Setting Reset signal SettingJog operation using external signals Use the optional FR-CB2 PID control valid terminal SettingPU operation/external operation switching Setting When connecting the parameter unitSystem configuration examples RS-485 communication4P Twisted pair cable, 4 pairs Wiring of one RS-485 computer and one inverter Wiring methodsMC1 Design InformationCommunication Parameters Only for the Type FunctionsFunction Parameter List Func- Pa- Indica- tion rame- tion ter Minimum Factory Cus Name Setting RangeMinimum Factory Refer Cus Name Setting Range FM AM THM, THT, GF OHT, OLT, PE, OPTPWM Selection functions PID ECL Alarm history 115 ClearFunc Tion CationNA, EC Com Minimum For details of the program, refer to page 118 onwardsList of Parameters Classified by Purpose of Use Related to monitoring Torque boost SettingName Factory Setting Remarks Explanation of Functions ParametersParameter Name Factory Setting Setting Range EC version Maximum and minimum frequencyBase frequency, Base frequency voltage EC version Remarks Range Multi-speed operation to toAcceleration/deceleration time Frequency setting Hz 120 Acceleration Deceleration time s Electronic overcurrent protection DC injection brakeOperation, etc. or the timing of operating Name Factory Starting frequencyLoad pattern selection Refer to Refer to , Name Factory Setting Setting Range RemarksJog frequency RUN key rotation direction selectionDeceleration Operation Not Activated Regenerative Driving Stall Prevention OL Signal Operation Fast OutputStall prevention function and current limit function CelerationDe Operation ActivatedStall prevention Where, a = 100Acceleration/deceleration pattern Set the acceleration/deceleration patternFunction Description Frequency jump Extended function display selectionSpeed display Use Pr , calibration parameter C4 for Biases and gains of the frequency setting voltage currentSetting Name Factory SettingSet value Hz How to change the highest frequencyFlicker ... Parameter setting complete OperationDisplayPress the SET key to set the value Voltage gain appears Press the SET key to show the analogTurn the setting dial to read another parameter Key to return toKey twice to show the next parameter Start-time ground fault detection selection Output Terminal Function ParametersUp-to-frequency sensitivity Output frequency detection On OFF Parameter Name Factory Setting Remarks RangeCurrent Detection Function Parameters Output current detection functionsZero current detection Display Function Parameters Monitor displayLED Setting dial function selection Press the RUN key to start the inverterRefer to Maximum output voltage of terminal AM is 5VDC Restart settingRestart Operation Parameters Monitoring referenceStfstr Setting DescriptionRefer to the following table and set the parameters Automatic restart operation afterAdditional Function Parameters Remote setting function selectionOr PU digital preset frequency Operation panel operation procedureFrequency setting storage conditions Pr SettingFunction E 2PROM Input terminal function selection Terminal Function Selection ParametersJOG Setting Signal Functions Related Parameters NameMRS REXReferred to Setting Signal Function Operation ParametersOutput terminal function selection Same function may be set to more than one terminalProtective Functions Major Failures for Retries Pr Setting Number of Retries Alarm Signal OutputOperation Selection Function Parameters Retry functionParameter Number Setting Description PWM carrier frequencyYou can change the motor sound Acceleration/deceleration time, which is a slope up/down to Applied motorVoltage input selection Set the motor usedReset Selection PU Stop Selection Setting Reset selection/PU stop selectionParameter Name Factory Setting Setting Range Remarks Setting RemarksOperation panel Restarting method with Shown Key input fromCooling fan operation selection Parameter write inhibit selection Pr Setting FunctionReverse rotation prevention selection Operation mode selectionRUN EXT Mode SignalFunction LED Indication * PU EXTMRS PU operation interlockOperation mode switching by external signal X16 Signal Operation ModePID control to Setting Basic PID control configuration PID action overview102 Variable output frequency if Deviation X = set point PID actionReverse action Increases the manipulatedRUNFUP,FDN Wiring exampleDeviation Negative105 O signalsParameter setting Name Setting Description106 Adjustment procedureEND Calibration example107 StartSet point input calibration Detector output calibration108 Automatic torque boost selection Auxiliary Function ParametersSlip compensation 11.2Operating conditions 110Ordinary V/F control and torque boost Pr , Pr are valid Meter frequency meter calibration Japanese version Parameter Name Factory Setting RemarksCalibration Parameters Motor primary resistance112 Flicker ... Parameter setting completeMeter frequency meter calibration NA and EC version When the FR-PU04 is used, make calibration with Pr 114 OperationDisplay Parameter clear Alarm history clearErases the alarm history Clear ParametersOperational functions Symbol Switching TypeOperation mode-based functions 118 Communication settings14.1 Communication-related parametersDescription Setting 119CR LF Computer programming Communication protocol Operation Run RunningInverter Monitor Parame 121 Data formatReply data from inverter to computer during data write Reply data from inverter to computer during data readControl codes Signal Ascii Code DescriptionData definitions Send data from computer to inverter during data readSTX ACK ENQ 123HFF 124Instruction Data H7FPage Setting items and set data 126FF = Nication Tion 127Calibra HECDescription Data Error Code ListError Definition 128Program example Operation at alarm occurrenceCommunication error General flowchartOperation and speed command write Location Selection N8 Pr Operation Command writeN9 Pr Speed Command write Explanation of table External Link start mode selectionN8 Pr operation Command write N10 Link start mode Setting is enabled when Pr = Selection14.4 E2PROM write selection 15.2 Parameter Unit FR-PU04 SettingParameter unit display language switching N13 Setting Display LanguageN16 100 PU contrast adjustmentN15 PU contrast adjustment Setting is enabled when Pr = PU main display screen data selectionPU disconnection detection/PU setting lock Monitor display and Resetstop key are validN17 Setting PU Disconnection Detection PU Setting Lock 136 FunctionsOC1 FR-PU04 Errors AlarmsError alarm definitions Major failuresOV1 FR-PU04 138OC2 FR-PU04 OC3 FR-PU04THT 139OV3 THMOPT FR-PU04 140OHT FR-PU04 OLT FR-PU04PUE Minor failuresFor only the type having the RS-485 communication function 141142 Write errors Er1 FR-PU04 Control Mode143 Er3 FR-PU04 Incr I/P Er2 FR-PU04 PU/EXT Mode144 Operator ERRResetting the inverter Correspondence between digital and actual charactersActual Display Motor remains stopped TroubleshootingMotor current is large Speed greatly differs from the settingMotor rotates in opposite direction Acceleration/deceleration is not smoothMotor produces annoying sound Operation mode is not changed properlyOperation panel display is not operating Parameter write cannot be performedPeriodic inspection Precautions for Maintenance and InspectionPrecautions for maintenance and inspection Check itemsInterval Daily Insulation resistance test using meggerPressure test Daily and periodic inspectionDaily 1 year 151Inspection Description IntervalInspection Interval Checking the inverter and converter modules Preparation Checking methodModule device numbers and terminals to be checked Inverter Model No Fan Type Replacement of partsPart Name Standard Replacement Interval Description Cooling fanAIR Flow Relays Smoothing capacitorsTypical Measuring Points and Instruments Measurement of main circuit voltages, currents and powersMeasuring Point Remarks Instrument Reference Measured Value Pf1=Pf2= 158Measuring Remarks Instrument Measuring PointRH, RM, RL, MRS RES-SD160 CationsSpecification List Phase 200V power supplyRatings Phase 400V power supply Single-phase 200V power supply Single-phase 100V power supply Common specifications NA, EC Outline Drawings 168 Parameter unit FR-PU04 Outline drawing Panel cut dimension drawing170 InstructionsPeripheral Selecting Instructions Selecting InstructionsHandling of secondary side magnetic contactor Installation of thermal relayDisuse of power factor improving capacitor power capacitor Handling of primary side magnetic contactorOperation Cable thickness and wiring distanceWiring Operating InstructionsPower supply InstallationInverter-driven 400V class motor Rectifying the motor insulationSuppressing the surge voltage on the inverter side 176 AppendixLink Data Func- Parameter tion NumberData Code Computer Extension178 Data Code Computer Link Parameter ExtensionRead 179 180 Name Link Data Tion Link Parameter Extension Setting Data Code 7F/FF181 Data Code Computer FuncPrint Date Manual Number Revision Manual number is given on the bottom left of the back cover