Mitsubishi Electronics FX-485ADP, FX0N-485ADP manual Examples of two-pair wiring for RS-422 circuit

Page 5

2.1Examples of two-pair wiring (for RS-422 circuit)

(1)When connecting one computer and one PC

485PC-IF

Cable connection and signal direction

485PC

Application

Signal name

Signal name

 

 

SDA

R*1

 

RDA

Reception data

SDB

 

R*1

Reception data

 

 

RDB

RDA

R*1

 

SDA

Transmission data

RDB

 

R1

Transmission data

 

 

SDB

LINK SG

 

LINK SG

Signal ground

Grounding

 

FG *2

Frame ground

 

24V *3

Power supply terminal

resistance of

DC24V

100 Ω or less

24G *3

Power supply terminal

FX base unit

(2)Computer and PCs in 1 : n connection ( n has a maximum value of 16 ).

The terminal lagout shown is diagrammatic only. As for 485ADP, see chapter 1, and as for 485PC-IF, and computer link unit for A series PC, see the individual manuals.

Computer

SD

RD

485PC-IF

485ADP

485ADP

Computer link unit

of A series PCs

 

 

 

 

 

 

Station

Station

Station

 

R *1

No. 0

No. 1

No. 15

 

 

SDA

SDA

SDA

SDA

*1

 

 

 

 

 

R

SD

SDB

SDB

SDB

SDB

 

 

 

 

 

 

R

*1

RDA

RDA

RDA

 

 

RDA

*1

 

 

 

 

 

R

RD

RDB

RDB

RDB

RDB

 

 

 

 

 

 

 

LINK

LINK

LINK

SG

 

 

SG

SG

SG

 

 

 

 

 

 

*2

*2

*2

 

 

 

FG

FG

FG

 

*1 R is the terminating resistance. Connect the terminating resistance (330 Ω) between terminals

SDA and SDB , and terminals RDA and RDB . For details see section 2.3.

*2 Connect terminal FG to earth terminal

of the PC main body grounded with resistance of 100

Ωor less. However, as for the computer link unit of the A series PC, see the manual of the computer link unit.

*3 The 24V DC power requirement can be taker from the service power supply of the PC.

Image 5
Contents FX0N-485ADPCOMMUNICATION Adapter Users GuideWeight Approx .3 kg 0.66 lbs Units mm inches External dimensionsIntroduction 〈FX-485ADP〉System configuration Connection with PC WiringApplicable PCs When connecting one computer and one PC Examples of two-pair wiring for RS-422 circuitExamples of one-pair wiring for RS-485 circuit Terminating resistances Power source specification and type of isolation SpecificationsEnvironmental specifications PC commands Command and Device RangeComputer commands Diagnostics Start UP Procedure Manual number JY992D53201 Manual revision C Data August