1.3 Applicable PCs

For setting up the system, the 485ADP can be connected to the following PCs.

 

PC series

PC version

Remarks

FX0N-485ADP

FX0N

Ver. 1.20 or later

Exclusive protocol format 1 and format 4 are supported.

FX-485ADP

FX , FX2C

Ver. 3.30 or later

Exclusive protocol format 1 and format 4 are supported.

As for exclusive protocol formats (1, 4) , see the 485PC-IF manual.

1.4 Connection with PC

For connection with the PC, connect the serial port provided at the left side facing the PC basic unit and the extension cable of the 485ADP. It must be noted however that only one special adapter (FX-8AV, FX-232ADP, etc.) such as 485ADP can be connected to the PC.

In the case of FX0N-485ADP

In the case of FX-485ADP

 

M IT S U B IS H I

 

RD A

 

RDB

 

SDA

 

SD B

 

SG LINK

 

F G

 

24+

 

24G

 

F X - 4 8 5 A D P

 

 

 

 

2

 

WIRING

 

 

 

 

 

The connecting method with the 485PC-IF is available in two-pair wiring and one-pair wiring, which may be used as follows. As for connection of the 485PC-IF and computer, see the 485PC-IF manual.

Two-pair wiring is required when :

The RS-422 device is incorporated in the system configuration.

A high speed response is required (message waiting time* is desired to be less than 70 ms).

The on-demand function is used (however, the system configuration must be 1 : 1).

Adding to a system already using two-pair wiring. *See the 485PC-IF manual.

One-pair wiring is required when :

Adding to a system already using one-pair wiring.

The system configuration is standardized to RS-485 devices, and two-pair wiring is not needed.

Image 4
Contents Users Guide FX0N-485ADPCOMMUNICATION AdapterExternal dimensions Weight Approx .3 kg 0.66 lbs Units mm inchesIntroduction 〈FX-485ADP〉System configuration Applicable PCs WiringConnection with PC Examples of two-pair wiring for RS-422 circuit When connecting one computer and one PCExamples of one-pair wiring for RS-485 circuit Terminating resistances Environmental specifications SpecificationsPower source specification and type of isolation Computer commands Command and Device RangePC commands Diagnostics Start UP Procedure Manual number JY992D53201 Manual revision C Data August