Mitsubishi Electronics FX-485ADP, FX0N-485ADP manual Terminating resistances

Page 7

2.3 Terminating resistances

The terminating resistances are resistances connected between terminals SDA and SDB, and between terminals RDA and RDB at both end stations of the circuit (or the interface when an interface such as 485PC-IF is used at both end stations), when connecting with the RS-485 or RS-422 circuit. For connection examples, see section 2.1 and 2.2.

Classification of terminating resistances

In this product, two sets of terminal end resistances (330 Ω 2, 110 Ω 1) are packaged, and the terminating resistances to be connected differ as shown below depending on the circuit being used.

When communicating with the RS-422 circuit, connect the resistances of “330 Ω 1/4W ” as the terminating resistances.

When communicating with the RS-485 circuit, connect the resistances of “110 Ω 1/2W ” as the terminating resistances.

330 Ω〉

 

 

 

 

 

 

 

 

 

110 Ω〉

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Orange

 

Brown

 

 

 

Brown

 

Orange

Two-pair wiring

 

 

 

 

One-pair wiring

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SDA

 

 

Terminating resistance

 

 

SDA

 

 

 

 

 

 

 

SDB

 

 

(330 Ω)

 

 

SDB

 

 

 

 

 

 

 

RDA

 

 

Terminating resistance

 

 

RDA

 

 

Terminating resistance

 

 

RDB

 

 

(330 Ω)

 

 

RDB

 

 

(110 Ω)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2.4 Cautions for wiring

As one of the conditions for exhibiting the function of the 485ADP sufficiently and building up a reliable system, external wiring resistant to noise is essential. Cautions for external wiring are given below.

(1)In this system, the data is read or written (turned on or off by force) while the PC is operating. Accordingly, if abnormal data is written into the PC due to effect of noise, the PC may malfunction, leading to machine trouble or accident, and therefore the following cautions should be strictly observed.

Never lay near or bundle together with the main circuit, high voltage line or load line. Or effects of noise or surge induction may be serious. Keep at least a safe distance of over 100 mm from these lines.

Ground the shield wire or shield of shield cable at one point at the PC side. Never ground commonly with high voltage line.

(2)Terminals screws of terminal block for RS-485 are M3 threaded. Therefore, connect wiring by fitting a crimped terminal suited to the terminal screws (see below) to the cable.

6.2mm (0.24 inches) or less

M3

 

M3

threads

6.2 mm

threads

 

 

 

(0.24 inches)

 

 

or less

 

(3)Tightening torque of terminals is 0.5 to 0.8 N·m (5 to 8 kgf·cm). Screw terminals must be secure enough to prevent a loose connection from causing a malfunction.

Image 7
Contents FX0N-485ADPCOMMUNICATION Adapter Users Guide〈FX-485ADP〉 External dimensionsWeight Approx .3 kg 0.66 lbs Units mm inches IntroductionSystem configuration Applicable PCs WiringConnection with PC When connecting one computer and one PC Examples of two-pair wiring for RS-422 circuitExamples of one-pair wiring for RS-485 circuit Terminating resistances Environmental specifications SpecificationsPower source specification and type of isolation Computer commands Command and Device RangePC commands Diagnostics Start UP Procedure Manual number JY992D53201 Manual revision C Data August