Bosch Appliances D9210C manual Event Profile, # Access Granted?, # No Entry?

Page 12

12 en Event ProfileAccess Control Interface Module

4

Event Profile

This programming category is used to determine if events are created for:

Access Ganted and Access Denied.

Door Requests.

Door state changes due to manual (command center) or automatic scheduled or armed state changes (skeds/hold open on disarm, normal on armed) operation.

Door #

Default:1

Selections1-8

Enter the door you are about to program.

NOTICE!

RTE events require Access Granted to be programmed [YES].

D# Access Granted?

Default:No

Selections:

Yes or No

 

 

This program item determines if ACCESS GRANTED and DOOR REQUEST events are sent to the panel for processing memory, printing, and remote reporting.

A successful access event can be initiated by a:

Valid user ID.

Valid door state changed at the command cener.

Automatically scheduled or armed state changes that hold a door open.

Request to enter/exit [RTE/REX].

Yes Access events from this door controller will be sent to the panel for processing. No Access events from this door controller will not be sent to the panel for processing.

D# No Entry?

Default:No

Selections:

Yes or No

 

 

This program item determines if No Entry events are sent to the panel for processing memory, printing, and remote reporting.

A No Entry event may be caused by:

Invalid or unknown user ID, interlock or secured door, or incorrect authority level.

Request to enter/exit [RTE/REX] for door in interlock or secured door.

Yes Access denied events from this door controller will be sent to the panel for processing. No Access denied events from this door controller will not be sent to the panel for processing.

F.01U.201.526 02 2011.10

Program Entry Guide

Bosch Security Systems, Inc.

Image 12
Contents Access Control Interface Module Page Table of Contents 1Trademarks About This DocumentOther Lettering Conventions used in this document Door Profile Door ## Entry Area # # CC# Scope# Door Point # Interlock Point# Auto Door? # Fire Unlock?# Disarm On Open? En Door Profile Access Control Interface Module Strike Profile # Strike Time# Shunt Time # Buzz Time# Extend Time # Deact On Open?# RTEShunt Only? # REXShunt Only? # Access Granted? Event Profile# No Entry? # Enter Request? # Exit Request?1Notes 5Program Record Sheets Summary account informationDoor # Point #Point TextLocation Door Yes/NoPage Bosch Security Systems, Inc