Bosch Appliances D9210C manual # Auto Door?, # Fire Unlock?, # Disarm On Open?

Page 7

Access Control Interface Module

Door Profile en

7

 

 

 

D# Auto Door?

Default:No

Selections:

Yes or No

 

 

Use this program item to unlock the door (latched shunt and strike) automatically when the entry area is disarmed. The door will re-lock upon Master or Perimeter Arming the area

Yes When the area assigned in D# Entry Area # is disarmed, the door will be in the Unlocked state. When that area is armed, the door will return to the Locked state.

No Door state will not be affected by the armed state of the area.

NOTICE!

The Unlocked state cannot be overridden manually.

NOTICE!

Doors that are activated by Fire Unlock must be returned to normal using the Door Control function on the control center.

D# Fire Unlock?

Default:No

Selections:

Yes or No

 

 

Use this program item to activate the relay for the door strike and shunt the door zone automatically upon a Fire Alarm. This feature will override a Secure Door state, Locked Door state, Auto Door, and an Interlock faulted point. The relay will activate for all doors with this prompt programmed [YES] when a Fire Alarm occurs in any area. Relays that are activated by Fire Unlock can only be returned to normal through the Command Center using the Door Control function.

Yes Relay will activate and shunt will be applied for the door contact automatically upon a Fire Alarm.

No Door will remain in its current mode upon a Fire Alarm.

DANGER!

This will unlock the door regardless of the armed state.

D# Disarm On Open?

Default:No

Selections:

Yes or No

 

 

Use this program item to determine whether the door needs to be physically opened prior to disarming the area upon a valid access request. The user initiating the access request must have access levels that allow disarming with ID.

Bosch Security Systems, Inc.

Program Entry Guide

F.01U.201.526 02 2011.10

Image 7
Contents Access Control Interface Module Page Table of Contents About This Document 1Trademarks Other Lettering Conventions used in this document # CC# Scope Door ProfileDoor # # Entry Area ## Interlock Point # Door Point# Fire Unlock? # Auto Door?# Disarm On Open? En Door Profile Access Control Interface Module # Buzz Time Strike Profile# Strike Time # Shunt Time# Deact On Open? # Extend Time# RTEShunt Only? # REXShunt Only? Event Profile # Access Granted?# No Entry? # Exit Request? # Enter Request?1Notes Summary account information 5Program Record SheetsDoor # Point #Point TextLocation Yes/No DoorPage Bosch Security Systems, Inc