10 en Strike Profile | Access Control Interface Module |
|
|
Blank Buzz Time is not programmed for this door.
D# Extend Time
Default:10
Selections: | Blank, |
|
|
Enter the amount of time that strike, buzz and shunt activation will be prolonged if a door is left open and the shunt time expires. At the end of the programmed extend time, the buzzer will continue to buzz until the door is closed. In addition, if programmed, the point assigned to the door will indicate a Trouble, Alarm or Fault at the command center.
NOTICE!
CLOSE DOOR # display on Command Center will not activate if no time (blank) is programmed.
NOTICE!
Regardless of how the door point is programmed, the system will generate a Trouble Door Left Open event while the system is disarmed and an Alarm Door Left Open event if the system is armed and the door is held open beyond Extend Time. Door Closed Restoral events are generated after the door is held open past Extend Time and the door has returned to normal.
D# Deact On Open?
Default:No
Selections: | Yes or No |
|
|
This program item determines whether the strike will deactivate immediately upon physically opening the door.
Yes Strike will deactivate when the door is opened after a valid access granted request.
No Strike will remain activated for the amount of the programmed strike time whether door is opened or closed.
NOTICE!
In order for this function to work a point needs to be assigned to the door.
TO REDUCE FALSE ALARMS: We recommend that you maintain this programming item as defaulted [YES]. This will help prevent the door from “bouncing” open and causing a false alarm.
D# RTEShunt Only?
Default:No
Selections: | Yes or No |
|
|
Use this program item to disable the strike, but still activate the programmed shunt time upon a Request to Enter an area.
F.01U.201.526 02 2011.10 | Program Entry Guide | Bosch Security Systems, Inc. |