STUDER Innotec Xtender
Installation and operating Instructions Xtender V1.3 Page 24
Auto restart
Absorption
Float
Input limited
Load search
Overload
Overtemp.
Bat. over volt.

Multimode Power Centre

Blinking indicator
X
TH-5000-24
Inverter + Charger + Autom. transfer + Input current manager
46
45
44
43
42
41
6.4.2 BTS-01 TEMPERATURE SENSOR
The operating voltages for lead batteries vary depending on the
temperature. A temperature sensor is optionally available to correct the
battery voltage and guarantee an optimum charge whatever the battery
temperature. The correction factor given by the correction of the sensor is
set by the configuration {1139}
Article no. for the temperature sensor (including a cable of 3 m): BTS-01.
Dimensions: H x W x D / / 58 x 51.5 x 22 mm

7 Control

7.1 Main on/off control

This switch (1) interrupts the electronic supply and all the
Xtender peripherals. The residual consumption on the
battery is therefore less than 1 mA.
The ON/OFF switch is used only for the complete
stoppage of the whole system.

7.2 Display and control parts

The Xtender has a ON/OFF button and light indicators at
the front of the device, allowing clear identification of
the operating mode.
(41) The ON/OFF button allows the startup or
complete stoppage of the system such as it has been
programmed. In the systems comprising several units,
each unit is started or stopped individually. For a
simultaneous startup of all the units use the dry contact
control (see chap. 6.2.12 – p. 21) or the ON/OFF
button of the RCC-02/03 remote control.
Even when the equipment has stopped,
dangerous voltages may be present at the
Xtender input.
(42) This indicator lights up when the equipment has been stopped manually using the ON/OFF
button (41). It also allows the cause of an unintentional stoppage of the device to be indicated via
the different flashes, the imminence of a stoppage or the temporary limitation of its performance.
The table below describes the type of fault according to the number of flashes on the indicator (42)
Indicated alarm Comment
1x (Imminent) stoppage as a
result of low battery voltage.
If the device has not yet stopped, it is recommended to
disconnect all non-priority consumers and/or start up the
generator. If the Xtender has stopped it will restart
automatically when the battery voltage has reached the correct
value again {1110}. It can be restarted manually using the
ON/OFF button (41) as long as the battery voltage is higher
than the critical threshold {1488}.
See also chapter 6.2.9 – p. 20.