STUDER Innotec | Xtender |
6.4.2
The operating voltages for lead batteries vary depending on the temperature. A temperature sensor is optionally available to correct the battery voltage and guarantee an optimum charge whatever the battery temperature. The correction factor given by the correction of the sensor is set by the configuration {1139}
Article no. for the temperature sensor (including a cable of 3 m):
Dimensions: H x W x D / / 58 x 51.5 x 22 mm
7 Control
7.1 Main on/off control
This switch (1) interrupts the electronic supply and all the Xtender peripherals. The residual consumption on the battery is therefore less than 1 mA.
The ON/OFF switch is used only for the complete stoppage of the whole system.
7.2 Display and control parts
Multimode Power Centre
Inverter + Charger + Autom. transfer + Input current manager
XTH-5000-24
Blinking indicator
The Xtender has a ON/OFF button and light indicators at | 46 |
the front of the device, allowing clear identification of | |
the operating mode. | 45 |
(41) The ON/OFF button allows the startup or | |
complete stoppage of the system such as it has been | 44 |
programmed. In the systems comprising several units, | |
each unit is started or stopped individually. For a | 43 |
simultaneous startup of all the units use the dry contact | 42 |
control (see chap. 6.2.12 – p. 21) or the ON/OFF | |
button of the |
|
Even when the equipment has stopped, | 41 |
| |
dangerous voltages may be present at the |
|
Xtender input. |
|
Load search
Input limited
Float
Absorption
Auto restart
Overload
Overtemp.
Bat. over volt.
(42)This indicator lights up when the equipment has been stopped manually using the ON/OFF button (41). It also allows the cause of an unintentional stoppage of the device to be indicated via the different flashes, the imminence of a stoppage or the temporary limitation of its performance.
The table below describes the type of fault according to the number of flashes on the indicator (42)
| Indicated alarm | Comment |
1x | (Imminent) stoppage as a | If the device has not yet stopped, it is recommended to |
| result of low battery voltage. | disconnect all |
|
| generator. If the Xtender has stopped it will restart |
|
| automatically when the battery voltage has reached the correct |
|
| value again {1110}. It can be restarted manually using the |
|
| ON/OFF button (41) as long as the battery voltage is higher |
|
| than the critical threshold {1488}. |
|
| See also chapter 6.2.9 – p. 20. |
Installation and operating Instructions | Xtender V1.3 | Page 24 |