6.4.2BTS-01TEMPERATURE SENSOR

The operating voltages for lead batteries vary depending on the temperature. A temperature sensor is optionally available to correct the battery voltage and guarantee an optimum charge whatever the battery temperature. The correction factor given by the correction of the sensor is set by the configuration {1139}

Article no. for the temperature sensor (including a cable of 3 m): BTS-01.

Dimensions: H x W x D / / 58 x 51.5 x 22 mm

7 Control

7.1 Main on/off control

This switch (1) interrupts the electronic supply and all the Xtender peripherals. The residual consumption on the battery is therefore less than 1 mA.

The ON/OFF switch is used only for the complete stoppage of the whole system.

7.2 Display and control parts

Multimode Power Centre

Inverter + Charger + Autom. transfer + Input current manager

XTH-5000-24

Blinking indicator

The Xtender has a ON/OFF button and light indicators at

46

the front of the device, allowing clear identification of

the operating mode.

45

(41) The ON/OFF button allows the startup or

complete stoppage of the system such as it has been

44

programmed. In the systems comprising several units,

each unit is started or stopped individually. For a

43

simultaneous startup of all the units use the dry contact

42

control (see chap. 6.2.12 – p. 21) or the ON/OFF

button of the RCC-02/03 remote control.

 

Even when the equipment has stopped,

41

 

dangerous voltages may be present at the

 

Xtender input.

 

Load search

Input limited

Float

Absorption

Auto restart

Overload

Overtemp.

Bat. over volt.

(42)This indicator lights up when the equipment has been stopped manually using the ON/OFF button (41). It also allows the cause of an unintentional stoppage of the device to be indicated via the different flashes, the imminence of a stoppage or the temporary limitation of its performance.

The table below describes the type of fault according to the number of flashes on the indicator (42)

 

Indicated alarm

Comment

1x

(Imminent) stoppage as a

If the device has not yet stopped, it is recommended to

 

result of low battery voltage.

disconnect all non-priority consumers and/or start up the

 

 

generator. If the Xtender has stopped it will restart

 

 

automatically when the battery voltage has reached the correct

 

 

value again {1110}. It can be restarted manually using the

 

 

ON/OFF button (41) as long as the battery voltage is higher

 

 

than the critical threshold {1488}.

 

 

See also chapter 6.2.9 – p. 20.