STUDER InnotecXtender
17 Table of standard configurations
No. of | Denomination / description |
| Units | Fact. | Mod. |
|
config. |
|
| value | value |
| |
|
|
|
|
|
|
|
1107 | Maximum current of the AC source |
| A | 30 |
|
|
1108 | Undervoltage of the empty battery |
| V/cell | 1.93 |
|
|
1109 |
| V/cell | 1.75 |
|
| |
1110 | Restart voltage of the inverter after undervoltage of the battery | V/cell | 2 |
|
| |
1111 | Automatic startup at power up |
| y/n | no |
|
|
1112 | Inverter frequency |
| Hz | 50 |
|
|
1121 | Maximum DC voltage for stopping the Xtender | V/cell | 2.84 |
|
| |
1126 | Source assistance (Smart Boost) permitted | y/n | no |
|
| |
1138 | Battery charge current |
| A | 60 |
|
|
1139 | Battery voltage correction according to the temperature | mV/°C/ |
|
| ||
|
|
| cell |
|
|
|
1140 | Battery maintenance voltage |
| V/cell | 2.27 |
|
|
1143 | Voltage 1 to allow a new battery cycle | V/cell | 2.1 |
|
| |
1144 | Duration of under voltage 1 to allow a new cycle | min. | 30 |
|
| |
1145 | Voltage 2 to allow a new battery cycle | V/cell | 1.93 |
|
| |
1146 | Duration of under voltage 2 to allow a new cycle | sec. | 180 |
|
| |
1156 | Battery absorption voltage |
| V/cell | 2.4 |
|
|
1157 | Duration of absorption |
| h | 2 |
|
|
1159 | Current at end of absorption |
| Adc | 10 |
|
|
1161 | Minimum interval between absorptions | h | 3 |
|
| |
1187 | Sensitivity of the charge detection (100% approx.25W) | % | 10 |
|
| |
1189 | Time interval between load search pulses | sec. | 0.8 |
|
| |
1190 | Duration of undervoltage of battery before disconnection | min. | 3 |
|
| |
1191 | Dynamic compensation for undervoltage | y/n | yes |
|
| |
1194 | Battery adaptive low voltage allowed |
| o/n | non |
|
|
1195 | Max voltage for adaptive low voltage |
| V/cell | 2.08 |
|
|
1198 | Time elapsing before transfer relay opens | sec. | 8 |
|
| |
1199 | ACin voltage causing the opening of the transfer relay | Vac | 180 |
|
| |
1200 | Immediate open critical threshold for the transfer | Vac | 50 |
|
| |
1246 | Auxiliary contact 1 activated by voltage 1 {1247} after delays | y/n | yes |
|
| |
| {1248} |
|
|
|
|
|
1247 | Voltage 1under which auxiliary contact 1 is activated | V/cell | 1.95 |
|
| |
1248 | Delays on voltage 1 to activate auxiliary contact 1 | min. | 1 |
|
| |
1249 | Auxiliary contact 1 activated by voltage 2 {1250} after delays | y/n | yes |
|
| |
| {1251} |
|
|
|
|
|
1250 | Voltage 2 under which auxiliary contact 1 is activated | V/cell | 2 |
|
| |
1251 | Delays on voltage 2 to activate auxiliary contact 1 | min. | 10 |
|
| |
1252 | Auxiliary contact 1 activated by voltage 3 {1253} after delays | y/n | yes |
|
| |
| {1254} |
|
|
|
|
|
1253 | Voltage 3 under which auxiliary contact 1 is activated | V/cell | 2.05 |
|
| |
1254 | Delays on voltage 3 to activate auxiliary contact 1 | min. | 60 |
|
| |
1255 | Voltage 1above which auxiliary contact 1 is deactivated after delays | V/cell | 2.25 |
|
| |
1256 | Delays on voltage {1255} to deactivate auxiliary contact 1 | min. | 60 |
|
| |
1258 | Auxiliary contact 1 activated by power 1 | y/n | yes |
|
| |
1259 | Power 1 above which auxiliary contact 1 is activated after delays | % | 120 |
|
| |
1260 | Duration of power 1 for activating auxiliary contact 1 | min. | 1 |
|
| |
1261 | Auxiliary contact 1 activated by power 2 | y/n | yes |
|
| |
1262 | Power 2 above which auxiliary contact 1 is activated after delays | % | 80 |
|
| |
1263 | Duration of power 2 for activating auxiliary contact 1 | min. | 5 |
|
| |
1264 | Auxiliary contact 1 activated by power 3 | y/n | no |
|
| |
1286 | Output voltage |
| Vac | 230 |
|
|
|
|
|
|
|
|
|
Installation and operating Instructions | Xtender V1.3 |
| Page 34 |
|