STUDER Innotec

Xtender

 

 

 

 

 

Elem.

Description

Comment

 

T

Non-secured grid

Distribution to users supplied exclusively via the present grid or the

 

 

 

generator.

 

 

 

This distribution is carried out in conformity with the local standards

 

 

 

and regulations.

 

U

Public grid

The connection to the public grid imposes adherence to the local

 

 

 

standards and regulations at the responsibility of the installer. The

 

 

 

installation should, in principle, be checked and approved by an

 

 

 

official body.

 

V

Automatic earth-

This connection is deactivated by default. In may be used in certain

 

 

neutral connection

specific cases for automatically re-establishing the neutral system

 

 

 

type TT (TNC, TNS, TNC-S) when the Xtender is in inverter mode.

 

 

 

The activation is carried out via RCC-02/03 remote control

 

 

 

configuration {1485}. This operation may only be carried out by

 

 

 

qualified personnel, under the responsibility of these personnel, and in

 

 

 

conformity with the local standards and regulations. See 4.2.3– p.11

 

W

Galvanic isolator

This device (optional) is generally used to reduce the risk of

 

 

 

electrolytic corrosion due to the direct current when a boat is

 

 

 

connected at the dock.

 

X

Source reversing

When the installation has more than one supply source, it is

 

 

switch

necessary to install a switching device between the sources,

 

 

 

simultaneously switching the neutral and the phase(s) of these

 

 

 

sources. In all cases this device (manual or automatic) must

 

 

 

guarantee interruption of the connected source before its connection

 

 

 

to another source.

 

Y

Isolation

This device (optional) prevents the risk of galvanic corrosion due to

 

 

transformer

direct currents when a boat is connected at the dock.

 

 

 

 

14 Elements of connexion cabinet (Fig 4a)

Pos.

Denomination

Description

 

 

 

 

Comment

 

 

1

ON/OFF

 

Main on/off switch

 

 

 

See chapter 7.1 - p 24.

 

 

 

Main switch

 

 

 

 

 

 

 

 

 

 

2

Temp. Sens

 

Connector

for

the

battery

See chapter 6.4.2 – p. 24.

 

 

 

 

 

temperature sensor

 

 

Only connect the original Studer BTS-01

 

 

 

 

 

 

 

 

 

 

sensor

 

 

3

Com. Bus

 

Double

 

connector

 

for

See chapter 4.5.9 – p. 14.

 

 

 

 

 

connecting peripherals such as

The two termination switches (4) for the

 

 

 

 

the RCC002/03

or

other

communication bus both remain in

 

 

 

 

Xtender units

 

 

 

 

position T (terminated) except when both

 

4

O / T

 

Switch

for

terminating

the

connectors are in use.

 

 

 

(Open

/

communication bus.

 

 

 

 

 

 

Terminated)

 

 

 

 

 

 

 

 

 

 

5

--

 

3.3 V (CR-2032) lithium ion type

Used as a permanent supply for the

 

 

 

 

battery socket

 

 

 

internal clock. See chapter 6.2.11 - p 21.

 

6

--

 

Jumper

for

programming

the

See chapter 6.2.12 – p. 21 and fig. 8b

 

 

 

 

off/on switch by dry contact

 

point (6) and (7). They are positioned at A-

 

 

 

 

 

 

 

 

 

 

1/2 and B-2/3 by default

 

 

7

REMOTE

 

Connection

terminals

for

dry

See chapter 6.2.12– p. 21).

 

 

 

ON/OFF

 

on/off remote connection.

 

When the control via dry contact is not

 

 

 

 

 

 

 

 

 

 

being used, a bridge must be present

 

 

 

 

 

 

 

 

 

 

between the two terminals.

 

 

8

AUXILIARY

 

Auxiliary contact

 

 

 

(See chapter 6.2.10– p. 21)

 

 

 

CONTACT

 

 

 

 

 

 

 

Take care not to exceed the admissible

 

 

 

 

 

 

 

 

 

 

loads

 

 

9

--

 

Activation indicators for auxiliary

See chapter 6.2.10– p. 21

 

 

 

 

 

contacts 1 and 2

 

 

 

 

 

 

Installation and operating Instructions

 

Xtender V1.3

Page 31

Page 31
Image 31
Studer Innotec XTH 8000-48, XTH 6000-48, XTH 5000-24 operating instructions Elements of connexion cabinet a, Pos