STUDER Innotec

 

 

 

 

Xtender

 

 

 

 

 

 

 

 

 

Pos.

Denomination

 

Description

 

 

 

Comment

 

10

L1/L2/L3

 

Phase selection jumpers.

 

See chapter 6.3.1. – p.22.

 

 

 

 

 

 

 

 

Jumper default at position L1

 

11

+BAT

 

Positive pole battery connection

Carefully read chapter 4.5 – p.12

 

 

 

 

terminals

 

 

 

Take care with the polarity of the battery

 

12

-BAT

 

Negative

pole

battery

and when tightening the clamp.

 

 

 

 

connection terminals

 

 

 

 

13

AC Input

 

Connection

terminals

for

the

See chapter 4.5.7 - p. 14.

 

 

 

 

alternative

power

supply

Note: It is imperative that the PE terminal

 

 

 

 

(generator or public network)

 

be connected.

 

14

AC Output

 

Connection

terminals

for

the

See chapter 4.5.6 - p. 14.

 

 

 

 

device output.

 

 

Note: Increased voltages may appear on

 

 

 

 

 

 

 

 

the terminals, even in the absence of

 

 

 

 

 

 

 

 

voltage at the input of the inverter.

 

15 Control and display parts for the Xtender (fig. 4b)

See chapter 7.2 - p. 24.

Pos.

Denomin

Description

 

 

Comments

 

ation

 

 

 

 

 

41

ON/OFF

ON/OFF button

The ON/OFF button allows the start up or complete stoppage

 

 

 

 

 

 

of the system such as it has been programmed. When there

 

 

 

 

 

 

are several units in the same system, each unit must be

 

 

 

 

 

 

started up or stopped individually using this button.

42

OFF

Light

indicator

When the light indicator flashes it indicates the cause of the

 

 

for stoppage

of

stoppage of the unit, its imminent stoppage or the limitation of

 

 

the unit

 

 

 

its rated power output according to chapter 7.2 - p.24.

 

 

 

 

 

43

ON

Light

indicator

This indicator is glowing continuously when the device is

 

 

showing that the

working. It flashes when the equipment is at a temporary

 

 

equipment

is

in

stop. Note: The equipment will restart automatically when the

 

 

operation

 

 

conditions that led to the temporary stoppage have gone

 

 

 

 

 

 

away.

44

Charge

Light

indicator

This indicator is glowing continuously when the charger is in

 

 

showing that the

operation and has not yet reached the absorption phase.

 

 

battery

is

being

It flashes twice during the absorption phase and once during

 

 

charged

 

 

 

the maintenance phase.

 

 

 

 

 

 

If smart boost mode has been activated it is possible that this

 

 

 

 

 

 

indicator will go out temporarily when source backup is

 

 

 

 

 

 

required by users. (See chapter 6.2.6 - p. 19)

45

AC in

Light

indicator

This indicator is glowing continuously when an alternative

 

 

showing

 

 

the

voltage with correct values is present at the AC IN input (13)

 

 

presence

 

of

of the device and the current limit {1107) set by the user has

 

 

correct

 

and

not been reached. It flashes when this limit is reached (see

 

 

synchronised

 

chapter 6.2.5 – p. 19).

 

 

input voltage

 

 

46

AC out

Light

indicator

This indicator is glowing continuously when an alternative

 

 

showing

 

 

the

voltage of 230V is present at the device output. It flashes

 

 

presence

of

a

when the device is in “load search” mode due to the absence

 

 

voltage

at

 

the

of users. (See chapter 6.2.3 – p. 16)

 

 

output

 

 

 

 

16 Type plate elements (fig. 1b)

Pos.

Denomination

Description

 

Comments

31

Model

Model

 

 

32

Pnom/P30

Rated power output / power for 30 minutes

 

 

 

 

 

 

Installation and operating Instructions

Xtender V1.3

Page 32

Page 32
Image 32
Studer Innotec XTH 5000-24, XTH 6000-48, XTH 8000-48 Control and display parts for the Xtender b, Type plate elements b