| STUDER Innotec |
| Xtender | ||
|
|
|
| ||
| 2x | Stoppage due to overload in | In this event the equipment will make several attempts restart | ||
|
| the equipment, due to either | {1133} every few seconds and will stop if the overload remains | ||
|
| a | (see chap. 6.2.9 – p. 20). It is vital to eliminate the cause of the | ||
|
| load for the inverter. |
| overload without restarting. Restarting is carried out manually | |
|
|
|
|
| by pressing the button (41). |
| 3x | Decrease in the rated output | This may be due to too great a load for the device, at too high | ||
|
| of the device due to a too | an ambient temperature or counteracted or obstructed | ||
|
| high internal temperature. |
| ventilation. The power output of the device will therefore be | |
|
|
|
|
| limited to around 50% of the Pnom. including in charger mode |
|
|
|
|
| or smart boost mode. |
|
|
|
|
| |
| 4x | Battery voltage higher than |
| Check the cause of this excess voltage. The equipment will | |
|
| the maximum limit set by the | restart automatically when the voltage falls below the threshold | ||
|
| configuration {1121}. |
| value {1122}. | |
|
|
|
|
| see chap. 6.2.9 – p. 20 |
| 5x | No transfer. Insufficient power | In this case, the Xtender remains in operation in inverter mode | ||
|
| from the source |
| until the output power decrease below the input limit and does | |
|
|
|
|
| not allow the transfer relay to close. You must increase the |
|
|
|
|
| input current limit {1107}, or authorise the exceeding of this |
|
|
|
|
| limit {1436} or authorise backup on the source {1126}, or |
|
|
|
|
| disconnect some consumers (decrease of loads). |
| 6x | Startup prevented due | to | Voltage is present at the device output. Check your cabling: | |
|
| unwanted | voltage at | the | correct the fault and start the installation again using a manual |
|
| device output. |
| control on the button (41). | |
| 7x | Indicates | missing voltage | on | Check the input protection devices (H) for all the system units. |
|
| one of the units of the system |
| ||
|
| in a |
|
(43)This indicator is glowing continuously when the device is working.
It flashes when the equipment is temporarily stopped due to a fault displayed by the indicator (42) or a ON/OFF control cabled at the ”Remote ON/OFF” input (7), or when the equipment is intentionally put to idle mode by the master unit in a
The equipment will restart automatically when the conditions that led to the temporary stoppage have gone away.
(44)This indicator is glowing continuously when the charger is working and has not yet reached his absorption phase.
It flashes twice during the absorption phase and once during the floating phase.
If the smart boost mode has been activated, this indicator goes out temporarily when source backup is required by users (loads).
(45)This indicator is glowing continuously when a n alternative voltage with correct values, either in frequency
If the smart boost mode (see chapter 6.2.6 – p.19) is used and the inverter is part of the user supply
– therefore the battery is discharged – the “charge” indicator (44) will be glowing.
(46)This indicator is glowing continuously when an alternative voltage of 230V is present at the equipment output. It flashes when the device is in “load search” mode according to chapter 6.2.2 – p. 16.
Installation and operating Instructions | Xtender V1.3 | Page 25 |