STUDER InnotecXtender

13 Figure element's (AC part)

Elem.

Description

Comment

 

 

A

Input supply cable

The section is determined by means of the maximum current at

 

 

 

source and the protection device (H). In multi-unit systems, cables (A)

 

 

 

of the same phase must have the same length and section (see

 

 

 

comment fig. 12-2/3).

 

 

 

 

 

B

Output

supply

In multi-unit systems, cables (B) of the same phase must have the

 

cable

 

same length and section (see comment fig. 12-2/3). The section must

 

 

 

be selected by means of the Xtender’s output current given on the

 

 

 

type plate and the protection device selected for the input (see fig.

 

 

 

1a).

 

 

C

Connection of the

See chapter 4.2 - p. 10.

 

 

neutrals

 

In a fixed installation where the neutral is connected to the earth at a

 

 

 

single installation point upstream of the Xtender, it is permissible to

 

 

 

carry out a connection of the neutrals in order to preserve an

 

 

 

unchanged earthing system downstream, independent of the

 

 

 

operating mode of the Xtender. This choice shows the advantage of

 

 

 

keeping the differential protection devices downstream of the

 

 

 

Xtender.

 

 

 

 

 

This connection (C) is not permitted if a socket is installed upstream

 

 

 

of the Xtender.

 

 

D

Differential

circuit

A protection device must be installed downstream of he source (G or

 

breaker

 

U) according to the local requirements and in compliance with the

 

 

 

applicable regulations and standards.

 

E

Earth-neutral

The neutral is earthed at a single point of the installation, downstream

 

connection bridge

of the source and upstream of the protection device(s) at the default

 

 

 

current (DDR). When several sources are available, each source must

 

 

 

have an earthed neutral. If the source has to be retained with an

 

 

 

isolated earthing system (IT) the applicable local provisions and

 

 

 

regulations must be applied.

 

F

AC

output

A protection device dimensioned in dependence of the cable section

 

protection devices

used may be installed downstream of the Xtender (main circuit

 

for the Xtender

breaker before distribution). The cable section is to be dimensioned

 

 

 

according to the calculation table of maximum output current (fig. 1).

 

 

 

The Xtender has an internal current limitation the value of which is

 

 

 

stated on the type plate Fig. 1b (35).

 

G

Generator

 

The generator is dimensioned according to the requirements of the

 

 

 

user. Its rated current will determine the configuration adjustment

 

 

 

{1107} “maximum current of the AC source”.

 

H

Protection devices

The protection device at the input of the Xtender must be

 

at the

Xtender

dimensioned according to the power output of the source at the

 

input

 

cable section used. It will not exceed a calibre equivalent to the input

 

 

 

current “I AC in” given on the type plate of the unit Fig. 1b (35).

J

 

 

 

 

 

K

Connection plug /

If the Xtender is connected to an AC source by means of a plug, the

 

socket

 

connection cable must not exceed a length of 2 m, and the socket

 

 

 

must remain permanently accessible. The socket will be protected by

 

 

 

a protection device of appropriate calibre. The connection of the

 

 

 

neutrals (C) is prohibited in this case.

 

L

 

 

 

 

 

P

 

 

 

 

 

R

 

 

 

 

 

S

Secured grid

Distribution to the users supplied by the grid or the generator when

 

 

 

this is present or by the Xtender within the limit of its power output

 

 

 

from energy stored in the battery. This distribution is carried out in

 

 

 

conformity with the local standards and regulations.

 

 

 

 

 

 

 

Installation and operating Instructions

Xtender V1.3

Page 30

Page 30
Image 30
Studer Innotec XTH 6000-48, XTH 8000-48, XTH 5000-24 operating instructions Figure elements AC part