Alarm beacon (optional)
1 . Install the alarm beacon in a visible position either on the roof of the rack or inside the rack.
2 . If you install the beacon on the roof, route its cable through the provided holes, as shown in the following illustration.
aem0061a
3 . Plug the cable into the Alarm Beacon port.
4 . You can extend the cable to a maximum of 100
m(330 ft), using
User inputs (optional)
There are four user input connection points provided on the Main Module. These inputs use screw terminal connections. Each may optionally be configured as:
•5 V dry contact input (Normally Open [N.O.] or Normally Closed [N.C.])
•
•
•
The graphics below and on the next page show example connections for N.O. and N.C. dry contacts,
User Inputs
+ +
Normally Open (N.O.) Contact
Closed for Alarm
User Inputs
+ +
Normally Closed (N.C.) Contact
Open for Alarm
aem0065a
aem0066a
Environmental Manager: Main Module | 13 |