Page 13

How to wire Modbus

The Modbus interface supports 2-wire RS-485, plus ground. Modbus can be configured to communicate at either 9600 or 19200 bps. The default setting is 9600 bps.

Modbus requires both termination and polarization resistors at the bus master. Each end of the bus requires a 150-ohm resistor, and the bus also requires

a400–650-ohm resistor from D1 to +5 Vdc and from D0 to GND.

SHIELD

TO

GND

UNIT 2

GD D N 0 1 D

SHIELD

TO

GND

CONTROLLER

+5V GND

D0 D1

499 OHM

499 OHM

TWISTED

PAIR

D0 & D1

UNIT 1

G D D

N 0 1

D

TWISTED

PAIR

D0 & D1

150 OHM

aem0069a

For more information, see the Modbus standard at www.modbus.org. Search for the Modbus Serial Line Implementation Guide.

Installation—Accessories

Sensors

Selecting a location for the sensor:

Install the sensor in a location that represents the air to be monitored. Avoid placing the sensor anywhere that may affect the sensor reading, such as near windows, room entrances, air ducts, other heat sources, or in direct sunlight.

Environmental Manager: Main Module

9

Image 13
Contents Installation and Quick Configuration Instrukcja Obsługi w jezyku polskim jest dostepna na CD Contents Recovering from a Lost Password Accessing a Configured Main ModuleTwo-Year Factory Warranty Life-Support PolicyOverview Preliminary InformationInventory QuantityAdditional documentation Please recycle Additional optionsReceiving inspection InfraStruXure-certifiedFront panel Front and Rear Panel ComponentsRear panel DescriptionDescription Toolless peg-mount installation Installation-Main ModuleRack-mount installation Connecting TH Modules Installation-TH ModuleAP9340 Main ModuleTH Module AP9341 Main Module AP9340 TH Module Adding power suppliesHow to wire Modbus Installation-AccessoriesSensors Selecting a location for the sensor To install a sensor on the vertical rail of an APC rack To install a sensor on the door of an APC rack To install sensors in another location User inputs optional Alarm beacon optionalCOM + PWR Overview TCP/IP Configuration MethodsBootp & Dhcp configuration APC Device IP Configuration WizardIni file utility Option 43 = 01 04 31 41 50 Local access to the control console Boot Mode Dhcp onlyAdvancedDHCP Cookie IsRemote access to the control console Choose Network from the Control Console menu Control consoleWeb interface Accessing a Configured Main ModuleSimple Network Management Protocol Snmp Telnet and SSHModbus FTP and SCPRecovering from a Lost Password Electrical Environmental Manager Main ModulePhysical EnvironmentalSensors Page Terms of warranty Two-Year Factory WarrantyNon-transferable warranty Exclusions Life-Support Policy Warranty claimsGeneral policy Examples of life-support devices Canada-ICES Radio Frequency InterferenceJapan-VCCI Taiwan-BSMIAustralia and New Zealand European Union 990-2379D-00111/2007 APC Worldwide Customer Support