5. EMI And Environmental Type Tests
Test |
| Description | Test Levels | |
IEEE C37.90.3 | ESD |
| Enclosure Contact | |
|
|
| ||
| Enclosure Air | |||
|
|
| ||
|
|
|
|
|
IEEE C37.90.2 | Radiated RFI |
| Enclosure ports | 35 V/m |
|
|
|
|
|
|
|
| Signal ports | +/- 4kV @ 2.5kHz |
|
|
|
|
|
IEEE C37.90.1 | Fast Transient |
| D.C. Power ports | +/- 4kV |
|
|
|
|
|
|
|
| Earth ground ports | +/- 4kV |
|
|
|
|
|
IEEE C37.90.1 | Oscillatory |
| Signal ports | 2.5kV common mode @1MHz |
|
|
| ||
| D.C. Power ports | 2.5kV common, 1kV diff. mode@1MHz | ||
|
|
| ||
|
|
|
|
|
IEEE C37.90 | H.V. Impulse |
| Signal ports | 5kV |
|
|
| ||
| D.C. Power ports | 5kV | ||
|
|
| ||
|
|
|
|
|
IEEE C37.90 | Dielectric Strength |
| Signal ports | 2kVAC |
|
|
| ||
| D.C. Power ports | 2kVDC | ||
|
|
|
aMeets Class 2 requirements for an
Table 5.2. IEEE 1613 (C37.90.x) EMI Immunity Type Testsa
Test | Description |
| Test Levels | |
IEC | Cold Temperature |
| Test Ad | |
|
|
|
|
|
IEC | Dry Heat |
| Test Bd | +85°C, 16 Hours |
|
|
|
|
|
IEC | Humidity (Damp Heat, Cyclic) |
| Test Db | 95% |
|
|
|
|
|
IEC | Vibration |
| 2g @ (10 - 150) Hz | |
|
|
|
| |
IEC | Shock |
| 30g @ 11mS | |
|
|
|
|
|
Table 5.3. Environmental Type Tests
RuggedCom® RuggedBackbone™ | 41 | RX1512 Installation Guide Rev 105 |