Powerware none UPS and Battery Care, Storing the UPS and Batteries, When to Replace Batteries

Page 27

Chapter 3

Maintenance

This section explains how to

SCare for the UPS and batteries

SReplace the Extended Battery Modules (EBMs)

SRecycle used batteries or UPS

UPS and Battery Care

For the best preventive maintenance, keep the area around the UPS clean and dust‐free. If the atmosphere is very dusty, clean the outside of the system with a vacuum cleaner.

For full battery life, keep the UPS at an ambient temperature of 25°C (77°F).

NOTE The batteries in the UPS are rated for a 3–5 year service life. The length of service life varies, depending on the frequency of usage and ambient temperature. Batteries used beyond expected service life will often have severely reduced runtimes. Replace batteries at least every 5 years to keep units running at peak efficiency.

Storing the UPS and Batteries

If you store the UPS for a long period, recharge the battery every

6 months by connecting the UPS to utility power. The batteries charge to 80% capacity in less than 5 hours. However, it is recommended that the batteries charge for 48 hours after long-term storage.

Check the battery recharge date on the shipping carton label. If the date has expired and the batteries were never recharged, do not use the UPS. Contact your service representative.

When to Replace Batteries

When the indicator flashes slowly and the audible alarm beeps intermittently, the batteries may need replacing. Contact your service representative to order new batteries.

EATON Powerware® BladeUPS® EBM User's Guide S 164201650 Rev 2 www.powerware.com

23

Image 27
Contents Powerware BladeUPS Extended Battery Module EBM Users Guide Special Symbols Table of Contents Table of Contents U T I O N Important Safety InstructionsSafety Warnings R N I N GVigtige Sikkerhedsanvisninger GEM Disse Anvisninger SikkerhedsanvisningerV a R S E L G E L E T Belangrijke Veiligheidsinstructies Bewaar Deze InstructiesBelangrijke Veiligheidsinstructies A R S C H U W I N GR O Tärkeitä Turvaohjeita Suomi Säilytä Nämä OhjeetTarkeita Turvaohjeita R O I T U SConsignes de Sécurité Consignes DE Sécurité Importantes Conserver CES InstructionsWichtige Sicherheitsanweisungen Aufbewaren SicherheitswarnungenH T U N G Avvisi di Sicurezza V E R T E N Z aT E N Z I O N E R S I K T I G Viktige Sikkerhetsinstruksjoner Gjem Disse InstruksjoneneViktig Sikkerhetsinformasion R L I GR I G O Instruções DE Segurança Importantes Guarde Estas InstruçõesRegulamentos de Segurança V E R T Ê N C I aПредупреждения по мерам безопасности ПредупреждениеОсторожно Advertencias de Seguridad V E R T E N C I aE C a U C I Ó N Viktiga Säkerhetsföreskrifter Spara Dessa Föreskrifter SäkerhetsföreskrifterK T I G T Inspecting the Equipment Chapter InstallationChecking the EBM Accessories EBM SetupRack Setup for the EBM Front Rail Screw Positions for the EBM Rear Rail Screw Positions for the EBM Slide the EBM into the rack Securing the EBM Mounting Brackets EBM Installation Typical EBM Installation Installation UPS and Battery Care When to Replace BatteriesStoring the UPS and Batteries How to Replace EBMs U T I O N Recycling the Used Battery or UPS Service and Support 1642016502