Raypak B6000 manual Installation and Mounting

Page 4

T-3 INSTALLATION AND MOUNTING

The T-3 Module should be mounted on a permanent base not subject to vibrations, moisture or dust. It should be readily accessible, for serviceability.

DIMENSIONS AND WEIGHT

15 3/4” H

14 LBS

8”

W

 

5 3/4”

D

 

MECHANICAL INSTALLATION

Mount the System Protocol Interface within five (5) feet of B6000 System Control Box.

The Gateway enclosure must be mounted vertically with conduit holes facing downward. Conduit holes are provided to accommodate standard conduit fittings. Additional or larger conduit fit- tings that may be required should be located on the bottom of the module. Mount the Interface with 3/8” or 1/4” hardware in four (4) places.

A Minimum of six (6) inches clearance on all sides is required and a minimum of eighteen (18) inches clearance from the front is required for service access. The hinged side of the box is to the right and the clearance (minimum 3” from bolt hole on the right side) should be sufficient to open the cover.

A sub-panel containing the disconnect switches and surge suppressors is required at or near the equipment location(s).

For accessibility remove the lower interior panel, by removing the four (4) access screws.

INSTALL CONDUIT AS APPROPRIATE.

ELECTRICAL CHARACTERISTICS

120 VAC, 0.25A, 60 Hz

ELECTRICAL INSTALLATION

120 VAC FEEDER CIRCUITS

Install a surge protection device sized appropriately for your installation.

Install separate disconnect means for each load. Pull in appropriately sized wire for equipment as defined by NEC and/or local code.

It is strongly recommended that the Communications Interface, B6000 System Control Module and the B6000 Boiler Control Module be supplied from the same source power.

4

Image 4
Contents Installation and Operating Manual Table of Contents Raypak B6000 System Protocol Interface Contents Quantity Installation and Mounting Wiring T-3 B6000 System Control Board Check Your Power Source Page 11.0.T-3 Product Specifications Command Error Checking Command TypesModbus Communications Data Integrity Modbus Register MapDip Switch Configuration SW1 Modbus Port ConfigurationIndicates Factory Setting 11.3.1.3 T-3 Jumper Configurations 11.3.2 B6000 CommunicationsModbus Commands Function Address Slave Driver Code Command Range CommentsModbus Error Codes Modbus Protocol SupportDiagnostics LED IndicatorsService and Repair ProSoft Support, Service and WarrantyTechnical Support Limited Warranty Appendix a Modbus Register MapBit Function Function Function Type DescriptionBoiler #1 Boiler #2 Boiler #3Boiler #4 Boiler #5Boiler #7 Boiler #6Boiler #8 40070 TS Boiler Start Times Sec Boiler #1
Related manuals
Manual 51 pages 14.6 Kb

B6000 specifications

The Raypak B6000 is a high-efficiency boiler designed for residential and commercial heating applications. Known for its reliability and advanced features, the B6000 exemplifies Raypak's commitment to engineering excellence and innovative technology.

One of the standout attributes of the Raypak B6000 is its robust construction. The boiler is built with high-quality materials, ensuring durability and longevity in a variety of environments. It features a compact design, which allows for easy installation even in spaces with limited room. Moreover, it has a user-friendly interface that facilitates straightforward operation and maintenance, making it accessible for both homeowners and HVAC professionals.

The B6000 is equipped with advanced heating technologies that enhance its performance and efficiency. It utilizes a modulating burner system that adjusts the heat output based on the demand, ensuring optimal energy usage. This not only leads to lower energy bills but also contributes to a reduced carbon footprint, making the B6000 an environmentally friendly choice.

Another key feature of the Raypak B6000 is its stainless steel heat exchanger, which provides superior heat transfer and contributes to the boiler's overall efficiency. The heat exchanger is designed to withstand high temperatures and pressures, ensuring safety and reliability throughout its operation. Additionally, the B6000 offers multiple venting options, including direct venting and horizontal venting, providing flexibility in installation.

The B6000 also comes with integrated controls that allow users to easily monitor and adjust settings. These controls can enhance energy efficiency by accommodating varying heating needs throughout the day. Furthermore, the boiler is compatible with smart home systems, enabling remote operation and monitoring.

In terms of safety features, the Raypak B6000 is equipped with multiple safety sensors and shutoff systems to ensure safe operation. This includes automatic shutdown in case of malfunction, preventing potential hazards.

Overall, the Raypak B6000 is a top-tier boiler that combines efficiency, reliability, and advanced technology, making it a preferred choice for those seeking a dependable heating solution. It is suitable for various applications, from residential heating to larger commercial projects, further establishing its versatility in the market. Whether for new installations or replacements, the B6000 stands out as a reliable option for efficient heating solutions.