5.Set the trip adjust pot to zero, fully counterclockwise (fully ccw).

6.Adjust the zero adjust pot so that the Red LED just does illuminate. This is a 25 turn pot. If the green LED is on, turn the pot counterclockwise (ccw). If red LED is on, turn the pot clockwise (cw).

7.Toggle the zero adjust pot back and forth until the switching point is well defined. Leave the Red LED illuminated.

8.Raise the level of the liquid to be detected until the probe/sensor tips are submerged and wet (covered).

9.Set the trip adjust pot to 100 (fully cw).

10.Adjust the span adjust pot so that the Green LED just does illuminate. This is a 25 turn pot. If the Green LED is on, turn the pot cw. If the Red LED is on, turn the pot ccw.

11.Toggle the span adjust pot back and forth until the switching point is well defined. Leave the green LED illuminated.

12.Adjust the trip adjust pot to 80 and the calibration is complete. Setting this pot to 80 gives an approximate equal trip time from wet to dry and from dry to wet. Setting this pot closer to zero will speed up dry to wet trip time and slow down wet to dry trip time. Setting this pot closer to 100 will slow down the dry to wet trip time and speed up wet to dry trip time.

IM-215 Rev-A.1

Series Innova-Switch™

Page 29 of 42

Image 29 Contents
INNOVA-SWITCH Series Before Starting Special Notice This manual covers the following model numbersTable of Contents Introduction Description Description IntroductionIM-215 Rev-A.1 Series Innova-Switch IM-215 Rev-A.1 Series Innova-Switch Thermal Differential Theory of Operation Level SwitchingFlow Switching Gas Or Liquid Flow Innova-Switch Model FS4200 Flow Response for Three Media IM-215 Rev-A.1 Series Innova-Switch Innova-Switch Models with the CE Option Switch Block Diagram Innova-Switch Switch Assembly Pipe or Vessel USE a 1 1/8 Inch 28.575mm OPEN-END InstallationWhen Installing Your Sierra Instruments Switch Into IM-215 Rev-A.1 Series Innova-Switch Innova-SwitchSWITCH Local Electronics Field Wiring Diagram Electrical InstallationIM-215 Rev-A.1 Series Innova-Switch Wiring Innova Switch Flow Switch Remote Electronics Option FieldRemote Electronics Cable Termination ConnectionsInnova-SwitchSWITCH Remote Electronics Field Wiring Diagram L.E.D. and Relay Status Logic Fail-safe Innova-Switch Electronics For Optimum OPERATION, Calibration Must be Accomplished Pre-Operational Check RED Green Relay Contact Sensor Status LED Innova-Switch Electronics Calibration Level IM-215 Rev-A.1 Series Innova-Switch IM-215 Rev-A.1 Series Innova-Switch Troubleshooting Intenance and Trouble ShootingCleaning Special Notice Operating Temperature Specifications TypeInput Power Process ConnectionsService Warranty and ServiceWarranty Connector Plates To Convert from Multiply by Volume Flow Conversion ChartFlow Conversion Chart Flow of Water Through Schedule 40 Steel Pipe Options Livetap LT Variable Insertion Thermocouple Output to and 10.4 RTD Output RT IM-215 Rev-A.1 Series Innova-Switch