4.0OPERATION AND CALIBRATION OF THE
4.1
With the switch installed and process conditions at
4.1.1Remove the instrument enclosure cover by turning counter clockwise (ccw) to expose the
4.1.2Turn on power at its source.
4.1.3Observe that either the red or green LED comes on.
4.1.4If neither lamp illuminates refer to the trouble shooting Section, 6.2.
4.2L.E.D. and Relay Status Logic (Fail-safe)
4.2.1The L.E.D.s (Red; Green) are an indication of the sensors status (ie. flow below the setpoint or flow above the set point) and are not affected by the position of the failsafe jumper
4.2.2Normal Operation (as set at factory)
The switch comes configured from the factory with the following operation with the
|
|
|
| RELAY | ||
| RED | GREEN | RELAY | CONTACT | ||
SENSOR STATUS | LED | LED | COIL STATUS | STATUS |
| |
No Flow or Flow Below Set Point | ON | OFF | Activated | o NC | ||
o NO | ||||||
|
|
|
| |||
Flow or Flow Above Set Point | OFF | ON | Deactivated | o NC | ||
o NO | ||||||
|
|
|
|
Series | Page 22 of 42 |