Westinghouse 30-471 (E) warranty 30-471 E

Page 5

Solid State Logic Control Panel

Type LRO Robonic II Automatic Transfer Switch

Rated 30 amperes through 100 amperes at 600 volts Ac maximum 50 or 60 Hertz.

The mechanism is a lever operated device controlled by a 120 volt unidirectional motor.

The transfer motor drives a nylon cam which in turn operates a steel lever by sliding a pin along a slot in the back of the lever. The lever, in turn, operates the two breaker handles. The distance travelled is determined by two projections on the cam. These projections operate two micro switches (NLS, ELS) which in turn disconnect the power to the transfer motor causing a brake to operate.

The type LRO has three operating positions. They are the normal breaker closed and the emergency breaker open, the emergency breaker closed and the normal breaker open or both the normal and emergency breakers open but never both normal and emergency breakers closed.

The type LRO can also be easily manually operated. Open the lever cover, remove the slide pin and place it in the hole supplied in the lever cover and close the cover. Then the lever can be manually operated for what ever position desired without interference by the automatic control. For automatic control again, simply align the lever slot with the hole in the operating cam and replace the slide pin.

The various automatic control components are described under the section titled “Logic Control”.

Instruction Leaflet

30-471 (E)

Page 5

Emergency

Normal

Slide

Pin

Projection To

Operate Limit Switch

Pivot Post

Operating Arm

Cam

Image 5
Contents Automatic Transfer Switch Instruction Leaflet You can be sure...if it’s Westinghouse For SupplyType RO Type LRO General Description30-471 E Spur Gear Meshing Relationship Type RO Robonic II Automatic Transfer SwitchType PRO Robonic II Automatic Transfer Switch Frequency Sensing Modules Interrupting, Closing and Withstand Rating Robonic Type aLogic Control Voltage Sensing Modules Time Delay Modules Type Dial Setting Pickup DropoutUndervoltage / Underfrequency Module Relay DriverDT and DTM Time Delay Relays Option #32A, 32B AdjustmentsUndervoltage Module Overvoltage ModulePlant Exerciser Option# 23A, 23B, 23C Transformer ModulesDescription ApplicationPortable Test Kit #50 Schematic of Robonic II Transfer Switch Parts List Replacing PartsParts Common to Robonic Plug-in Modules OptionsType LRO Robonics Trouble Shooting Guide Symptoms Possible CausesRecommended Maintenance