This time delay relay is an octual
When the timing cycle is complete, a mechanical latch holds the contacts in position and the coil is
Transformer Modules
Modules include all necessary control, voltage sensing and logic transformers.
Two versions are available. The standard module has three phase monitoring of the normal source and one phase monitoring of the emergency source. The optimal module has three phase monitoring on both the normal and emergency sources.
Plant Exerciser Option# 23A, 23B, 23C
Ratings - Input voltage 120 volts
Contact rating 20 Amps at 120 volts resistive S.P.D.T.
Description
Dial A is divided into a 24 hour day and night scale, and has tabs around the periphery which may be adjusted to operate the micro switch within intervals each 24 hours. Each tab represents a 15 minute interval. Dial B has 7 spokes and advances one position for each revolution of Dial A. Each spoke has provision to add a pin to operate the micro switch. These pins represent days of the week and their function is to prevent operation of the micro switches on selected days.
Application
The plant Exerciser is a Program Time Switch which functions to start and stop the
1.It may to simulate an interruption in the normal source of supply at selected intervals, at least once per week, causing the transfer switch components to function, including