Instruction Leaflet
30-471 (E)
Page 8
Both under and overfrequency cards are factory calibrated at 60 Hz. The actual values of pickup and dropout are as follows:
Type |
| Dial Setting | Pickup | Dropout | |
|
| Hz | Hz | Hz | |
Underfrequency | 60 | 57 |
| 55 | |
Underfrequency | 50 | 47 |
| 45 | |
Overfrequency | 60 | 63 |
| 65 | |
Overfrequency | 50 | 53 |
| 55 | |
Undervoltage / Underfrequency Module |
| ||||
S#1288C58G01 | Option# 5A, 26F |
|
|
| |
Monitors one phase of power source. |
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
Time Delay Modules |
| |
S#1275C74G01 | Option#1A, 3A, 4A | |
S#1275C74G02 | Option#1B, 3B, 4B | |
S#1275C74G03 | Option#1C, 3C, 4C | |
5 min fixed | S#1275C74G08 | Option#4D |
All can be used to accomplish TDEC, and TDNE functions.
Relay Driver
S#1266C77G02 | Option#1A, 1B, 1C, 3A, 3B, 3C, 4A, 4B, 4C, 4D |
This card is used in place of any of the timing modules when instantaneous operation is required.
Blank
S#1266C77G01
Used to cover any unused card slots.
All Cards Mechanically Interlocked
All cards are interlocked mechanically to prevent insertion into the wrong function slot. All cards have a repeat accuracy over a 20 to
+60°C temperature change of (+ or
After making adjustments, tighten locking screw to secure setting. Tighten mounting screws (screws are not captive).