Westinghouse 30-471 (E) Type Dial Setting Pickup Dropout, Undervoltage / Underfrequency Module

Page 8

Instruction Leaflet

30-471 (E)

Page 8

Both under and overfrequency cards are factory calibrated at 60 Hz. The actual values of pickup and dropout are as follows:

Type

 

Dial Setting

Pickup

Dropout

 

 

Hz

Hz

Hz

Underfrequency

60

57

 

55

Underfrequency

50

47

 

45

Overfrequency

60

63

 

65

Overfrequency

50

53

 

55

Undervoltage / Underfrequency Module

 

S#1288C58G01

Option# 5A, 26F

 

 

 

Monitors one phase of power source.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Time Delay Modules

 

1-60 sec. timer

S#1275C74G01

Option#1A, 3A, 4A

0.1-10 min. timer

S#1275C74G02

Option#1B, 3B, 4B

0.2-30 min. timer

S#1275C74G03

Option#1C, 3C, 4C

5 min fixed

S#1275C74G08

Option#4D

All can be used to accomplish TDEC, and TDNE functions.

Relay Driver

S#1266C77G02

Option#1A, 1B, 1C, 3A, 3B, 3C, 4A, 4B, 4C, 4D

This card is used in place of any of the timing modules when instantaneous operation is required.

Blank

S#1266C77G01

Used to cover any unused card slots.

All Cards Mechanically Interlocked

All cards are interlocked mechanically to prevent insertion into the wrong function slot. All cards have a repeat accuracy over a 20 to

+60°C temperature change of (+ or -) 3%. Dial settings are (+ or -) 10% of indication.

After making adjustments, tighten locking screw to secure setting. Tighten mounting screws (screws are not captive).

Image 8
Contents Automatic Transfer Switch Instruction Leaflet For Supply You can be sure...if it’s WestinghouseGeneral Description Type RO Type LRO30-471 E Spur Gear Meshing Relationship Type RO Robonic II Automatic Transfer SwitchType PRO Robonic II Automatic Transfer Switch Frequency Sensing Modules Interrupting, Closing and Withstand Rating Robonic Type aLogic Control Voltage Sensing Modules Type Dial Setting Pickup Dropout Time Delay ModulesUndervoltage / Underfrequency Module Relay DriverAdjustments DT and DTM Time Delay Relays Option #32A, 32BUndervoltage Module Overvoltage ModuleTransformer Modules Plant Exerciser Option# 23A, 23B, 23CDescription ApplicationPortable Test Kit #50 Schematic of Robonic II Transfer Switch Replacing Parts Parts ListParts Common to Robonic Plug-in Modules OptionsType LRO Robonics Trouble Shooting Guide Symptoms Possible CausesRecommended Maintenance