Schematic of Robonic II Transfer Switch
Consider the Robonic II in the normal operating position, with normal power available and the normal interrupter closed. The following are energized: U.V. (undervoltage module), TDES (time delay engine start), and NR (normal relay).
The U.V. monitoring all 3 phases of the normal power, senses a dip or loss of voltage which instantly causes NR to deenergize. Contacts NR2 and NR4 open, and contacts NR1 and NR3 close. TDES times out, closing it’s contacts and initiating the emergency system start up. When the emergency system reaches correct levels of voltage and frequency, ER is energized and contact ER2 closes. This completes the emergency control circuit, and TM (transfer motor) begins to operate.
First, the normal interrupter is opened, and then the emergency interrupter is closed. At this point, the ELS (emergency limit switch) contacts change state, and the BS (motor brake) closes, preventing TM over travel. The NLS (normal limit switch) contacts change state in preparation for
Upon return of stabilized normal power, NR is