Instruction Leaflet
30-471 (E)
Page 9
Adjustments
Timer and frequency modules can be adjusted as per module front plate. Voltage sensing modules can be adjusted as follows:
Undervoltage Module
Set Description
1Set Dropout knob maximum
2Set
3Increase line volts to desired Dropout value (normally 70%) LED should be “ON”
4Rotate Dropout Clockwise until LED goes “OFF”
5Rotate
6Increase line volts to desired
7Rotate
8
Overvoltage Module
Step Description
1Set Dropout to maximum Counterclockwise
2Set
3Set line voltage to pull in value desired (normally 105%) LED is “OFF”
4Rotate
5Rotate Dropout maximum Clockwise
6Set line voltage to Dropout value desired (normally 15%)
7Rotate Dropout Counterclockwise until LED is “OFF”
8Drop line voltage to
9Increase line voltage to desired Dropout value. LED should go “OFF”
DT and DTM Time Delay Relays Option #32A, 32B
Ratings - 6 Watts Power Consumption Input coil Voltage - 120 volts
Contact Rating - 3 amperes at 220 volts Ac 50/60 Hertz Operating Temperature Rating -
Time Ratings - Various available
The relay is incorporated in the control scheme to stop the transfer switch with both breakers open. This is to allow residual load voltage to decay prior to closing on another supply which could be out of phase. When the timing cycle is complete, the relay
Time Delay Engine Starting Relay
Solid State Type Option #2A
Ratings - 1.2 Watts Power Consumption
Input coil voltage - 120 volts at 50/60 Hertz.
Contact Rating - 10 amperes resistive at 120 volts
Time Range - 2 to 3 seconds - nonadjustable.
Operating Temperature Range -
Pneumatic Type Option #2B
Rating - 8 Watts Power Consumption
Input Coil Voltage - 120 volts 50/60 Hertz.
Contact Rating - 10 amperes resistive at 120 volts Ac. Time Ranges - Various available.
Operating Temperature Range -