Max continuous input voltage | 120% of nominal (up to 720V max.) |
Max short duration input voltage | 2*nominal (1s application repeated 10 times at |
| 10s intervals) |
Nominal input voltage burden | 0.2VA approx. per phase |
Nominal input current | 1 or 5A a.c. rms |
System CT primary values | Std. values up to 4kA (1 or 5 Amp secondaries) |
Max continuous input current | 120% of nominal |
Max short duration current input | 20*nominal (1s application repeated 5 times at |
| 5 min intervals) |
Nominal input current burden | 0.6VA approx. per phase |
4.3.2 Auxiliary Power Supply
The unit can be powered from an auxiliary a.c. or d.c. supply that is separate from the metered supply. Versions of the unit are available to suit
Standard supply voltage | 100 to 250V a.c. nominal ±15% (85V a.c. absolute |
| minimum to 287V a.c. absolute maximum) or 100V to |
| 250V d.c. nominal +25%, |
| minimum to 312V d.c. absolute maximum) |
a.c. supply frequency range | 45 to 66 Hz or 360 to 440 Hz (Model 0440) |
a.c. supply burden | 3W |
d.c.supply | 12 to 48V d.c.. nominal +25%, |
| minimum to 60V d.c. absolute maximum) |
d.c. supply burden | 3W |
4.3.3 Accuracy |
|
Voltage | 0.4% of reading ±0.1% of range |
Current | 0.4% of reading ±0.1% of range |
Neutral current | 4% of range |
Frequency | 0.15% of mid frequency |
Power factor | 1% of Unity |
Active power (W) | 0.9% of reading ±0.1% of range |
Reactive power (VAr) | 1.9% of reading ±0.1% of range |
Apparent power (VA) | 0.9% of reading ±0.1% of range |
Active energy (W.h) | 1 Class (IEC 1036, Active PF |
Reactive energy (VAr.h) | 2%, Reactive PF |
Temperature coefficient | 0.013%/°C typical |
Response time to step input | 1.5 seconds approx. |
Error change due to variation | Twice the error allowed for the reference |
of an influence quantity in the | condition applied in the test. |
manner described in section 6 |
|
Integra 1540, 1000, 0640, 0440, 0340, 0240 Issue 1 04/03 | 49 |