Tyco 1540 manual Usa

Page 39

When setting up the analogue output for a power factor reading, the Reading Top value must be in one of the left-hand quadrants and the Reading Bottom value must be in one of the right- hand quadrants.

Hence, if the Reading Top value is set to –0.5, this will be a power factor of 0.5 for power exported to an inductive load (bottom left-handquadrant). Conversely, the Reading Bottom value must be in one of the two right-hand quadrants. If the Reading Bottom value is set to –0.5, this will be a power factor of 0.5 for power exported to a capacitive load (bottom right-handquadrant). Thus a power factor of +1 (for true power imported to a resistive load) is always included in the analogue output range.

In specifying the Output Top and Output Bottom values, there are two conventions – one for European areas of influence and one for North American areas. The two conventions are:

Europe

Output Top greater or more positive than Output Bottom.

USA

Output Top less or more negative than Output Bottom.

The examples below show cases where power is only imported and the load may be either capacitive or inductive. The Reading Top and Reading Bottom values of zero ensure that the whole range of possible (import) power factor readings is covered. The unit in the left-hand example has an analogue output range of +1 to –1 mA and, since the Output Top value (+1 mA) is more positive than the Output Bottom value (-1 mA), this arrangement complies with the European convention. The right-hand example shows the North American convention.

In the above symmetrical arrangement, 0 mA corresponds to unity power factor. This is not the case with the following asymmetrical arrangement.

Integra 1540, 1000, 0640, 0440, 0340, 0240 Issue 1 04/03

37

Image 39
Contents Energy Division Crompton Switchboard Integra Contents Setting up Specification Basis of measurement and calculations Serial Communications Maintenance Appendix a CE Declaration of ConformityTHD Introduction3 0440 Unit CharacteristicsIntegra 1540, 1000, 0640, 0440, 0340, 0240 Issue 1 04/03 Default display Maximum Power Secondary VoltageDemand Calculation RS485 Serial Option Pulse Output OptionAnalogue Output Option Display Screens LayoutStart Up Screens System Screen System %THD Screen Line to Neutral VoltagesLine to Neutral Voltage %THD Line to Line Voltages Line to Line Voltages %THDLine Currents Neutral Current, Frequency and Power Factor PowerLine Currents %THD Reactive Energy kVArh Active Energy kWhDemand Maximum DemandOver Range Setting up Error MessagesKWh and kVArh Display Range Number Entry Procedure Integra 1540, 1000, 0640, 0440, 0340, 0240 Issue 1 04/03 Access Access with No Password ProtectionAccess with Password Protection Integra 1540, 1000, 0640, 0440, 0340, 0240 Issue 1 04/03 Changing the Password Potential Transformer Primary Voltage Full Scale CurrentIntegra 1540, 1000, 0640, 0440, 0340, 0240 Issue 1 04/03 Potential Transformer Secondary Value Demand Integration Time Resets Pulsed Output, Pulse Duration Pulse Rate 12 RS485 Baud Rate 13 RS485 Parity Selection 14 RS485 Modbus Address Reduced output range Analogue Output Set Up Second Channel Reverse OperationReading Bottom A1rb or A2rb Analogue Output Scaling ExampleReading A1r or A2r Reading Top A1rt or A2rtPower Factor Output Bottom A1ob or A2obSummary USA Reading European Convention North American Convention Output Phase Angle L1-L2 Calculated Reading Parameter Selection A1r or A2r Parameter Number WireReading Top A1rt or A2rt Reading Bottom A1rb or A2rb Display Only Versions SpecificationDisplay/Transducer Combined 0240, 0340, 0440 121 240V L-L 70.1 139V L-N Measuring Ranges AccuracyReference conditions of influence quantities Display/Tranducer Combined 1000 Auxiliary Power Supply Reference conditions Standards Nominal range of use of influence quantities for measurandsFunctional ranges ScreenModbus RS485 Serial Communications OptionIntegra 1540 Only Active Energy Pulsed Output OptionReactive and Apparent Power Energy resolutionBasis of measurement and calculations Total Harmonic Distortion 1540 only Serial Communications RS485 Port Modbus or JC N2Modbus Implementation Input Registers Parameter Modbus Start High Low Byte Modbus Holding Registers and Integra set upRS485 Implementation of Johnson Controls Metasys Application detailsMetasys release requirements Support for Metasys Integration Support for Crompton Integra operationDesign considerations Integra 1560/1580 Point Mapping table Metasys N2 applicationMaintenance Integra 1540, 1000, 0640, 0440, 0340, 0240 Issue 1 04/03 Integra 1540, 1000, 0640, 0440, 0340, 0240 Issue 1 04/03 Integra 1540, 1000, 0640, 0440, 0340, 0240 Issue 1 04/03