Perle Systems DS1, TS2 manual Hosts, Local connection

Page 155

Channels

Connect to

When enabled, the channel/serial signal pin initiates communication to another

 

I/O channel or a TCP/IP application.

 

Default: Enabled

Host Name

The configured host or another IOLAN that the I/O channel will connect to.

 

Default: None

TCP Port

The TCP Port that the channel/serial signal pin will use to communicate to

 

another IOLAN or a TCP/IP application.

 

Default: 2000 for channel 1, then increments by one for each channel

Connect to Multiple When enabled, input channel or serial signal pin can communicate to multiple

Hosts

hosts running a TCP/IP application or I/O channels.

 

Default: Disabled

Define Additional

Click this button to define the hosts/IOLANs that this channel or serial signal

Hosts Button

pin will connect to. This button is also used to define the Primary/Backup host

 

functionality.

Local connection

When this option is enabled, the input or output, depending on how the channel

 

or serial signal pin is configured, will be associated with another local IOLAN

 

I/O channel or serial signal pin.

 

z When the channel is configured as digital input or when configuring an

 

input serial signal pin, the Output Channels parameter displays all the

 

local digital output signals or relays that it is associated with.

 

z When the channel is configured as digital output, you must select a local

 

digital input channel or input serial signal pin on the IOLAN.

 

Note that the Failsafe Action is not compatible this option.

 

Default: Disabled

Enable TCP

Enables a per-connection TCP keepalive feature. After the configured number

Keepalive

of seconds, the connection will send a gratuitous ACK to the network peer, thus

 

either ensuring the connection stays active OR causing a dropped connection

 

condition to be recognized.

 

This parameter needs to be used in conjunction with Monitor Connection

 

Status Interval parameter found in the Serial, Advanced, Advanced Settings

 

tab. The interval determines how long the IOLAN will wait during inactivity

 

before "testing" the connection. It should be noted that if a network connection

 

is accidentally dropped, it can take as long as the specified interval before

 

anyone can reconnect to the serial port.

 

Default: Disabled

155

Image 155
Contents Iolan DS1/TS2 EN 55022 1998, Class A, Note Documentation PrefaceAbout This Book Intended AudienceOnline Help Typeface ConventionsTable of Contents Configuration Methods Getting Started Using DeviceManager and WebManager Serial Port Profiles Network Settings Configuring Users Configuring Security UDP Configuring the System Controlling the I/O Channels Appendix a Virtual Modem AT Commands Appendix D I/O Wiring Diagrams Appendix H Data Logging Appendix I Modbus Remapping 241 Iolan Family Models IntroductionAbout the Iolan Hardware Iolan FeaturesSoftware Security Iolan Components ConnectivityIntroduction Overview Power Supply SpecificationsGetting to Know Your Iolan Desktop ModelsSerial Activity DS1End View Top ViewSerial Mode Console/Serial SwitchConsole Mode Models with Terminal Block Connector Powering Up the IolanModels with Barrel Connector Configuration Methods Chapter Requires a Configured IP Address Configuration Methods OverviewConfigures an IP Address Easy Config Wizard DeviceManager Access PlatformsFeatures Connecting to the Iolan Using DeviceManagerDeviceManager Navigating the Options Using DeviceManagerWebManager Connecting to the Iolan Using WebManagerDownloading the Configuration WebManager Using WebManager Through the Network Command Line InterfaceConnecting to the Iolan Using the CLI Through the Serial Port Using the CLIConnecting to the Iolan Using the Menu MenuUsing the Menu Using DHCP/BOOTP Connecting to the Iolan Using DHCP/BOOTPDHCP/BOOTP Parameters Snmp Connecting to the Iolan Using SnmpUsing the Snmp MIB Getting Started Easy Configuration WizardSetting Up the Network Using a Direct Serial Connection to Specify an IP Address Using a Direct Serial Connection to Enable BOOTP/DHCP For an IPv6 Network Using ARP-PingSetting Up the Serial Ports Setting Up the Serial Ports Setting Up Users Using DeviceManager WebManager DeviceManager Navigating DeviceManager/WebManagerWebManager Starting a New Session Using DeviceManager to Connect to the IolanAssigning a Temporary IP Address to a New Iolan Logging in to the Iolan Adding/Deleting IOLANs ManuallyLogging into the Iolan Using WebManager to Connect to the IolanConfiguration Files Creating a New Iolan Configuration in DeviceManagerManaging the Iolan Opening an Existing Configuration FileImporting an Existing Configuration File Functionality Serial PortsEditing a Serial Port Resetting a Serial Port Hardware Tab Field Descriptions Serial Port ProfilesCommon Tabs OverviewEnable Inbound Default NoneDefault Full Default AutoPacket Forwarding Tab Field Descriptions Packet Size Enable Trigger1Enable Trigger2 Packet DefinitionFunctionality Console Management ProfileIP Address Default TelnetGeneral Tab Field Descriptions Protocol Listen for Connections on TCP PortAdvanced Tab Field Descriptions Dial Out Default 10 ms DialModem Dial TimeoutTruePort Profile Dial RetryTCP Port System Default Enabled Host NameConnect Default Disabled Define Additional Connect to remoteAdding/Editing Additional TruePort Hosts Primary Host Backup HostAdding/Editing a Multihost Entry When Signals highDay Motd Default Disabled Enable TCP Enable Data Logging Trueport Lite Mode Dial Retry TCP Sockets Profile Connection Workstation/Server on the network Default EnabledDefault Disabled Adding/Editing Additional Hosts Adding/Editing a Multihost Entry Lost Day Motd Default Disabled Enable DataDefault 10 ms Dial UDP Sockets Profile Serial Port Profiles UDP Entry End IP Address Connections onUDP port Direction Start IP AddressSession Strings Port UDP port to use Default 0 zeroDefault 10 ms Terminal ProfileVT320 specifically supporting VT320-7 Default DumbVT100 TVI925Received Default Disabled ProtocolWhen any data is AutomaticallyData Range Default Disabled Hotkey PrefixSession Timeout Login Settings User Service SettingsErase Telnet SettingsInterrupt QuitSerial Tunneling Profile Server Client Default Disabled Host NameAct As Tunnel Break Length Delay After BreakVirtual Modem Profile 100 DCD DTR Signal Acts as RTS Signal Always OnResponse Delay RTS Signal Acts asAT Command VModem Phone Number Entry Phone Number to Host MappingHost IP Address Control Signal I/O ProfilePhone Number Description Input Signal Field DescriptionsInvert Signal Auto Clear ModeFailsafe Action Output Signal Field DescriptionsMode Default Disabled Syslog Manual ClearModbus Gateway Profile Button IP address Advanced Slave Settings ButtonDestination Slave IP MappingsAdvanced Field Descriptions Default 30 msMessage Timeout Default 1000 msUID Start Modbus Slave IP Settings Field DescriptionsAdding/Editing Modbus Slave IP Settings Type Default HostDefault TCP UID EndModbus Slave Advanced Settings Field Descriptions General Tab Field Description Default OffCustom Application Profile Field Descriptions Advanced Serial Settings TabClosing Serial Port Default Disabled Deny Multiple AdvancedAdding/Editing a Modem Modems TabName Name of the modem Field Definitions TruePort Baud Rate TabNetwork Settings Domain IP SettingsIPv4 Settings System NameIPv6 Settings Adding/Editing a Custom IPv6 Address Advanced Default IPV6 68-1500 bytesDelete Button Deletes a host from the host table Host TableAdding/Editing a Host Add Button Adds a host to the host table Edit ButtonAdding/Editing Routes Route ListHost Default DefaultIPv4 Subnet Mask IPv6 Prefix BitsConfiguring Users User Settings General Tab Adding/Editing UsersLevel Default NormalHost IP Services TabService Default DSPromptLanguage Default EnglishAdvanced Tab Sessions Tab Connect Session 1, 2, 3Serial Port Access Tab Services Configuring SecurityField Descriptions Technical Specifications Configuring I/O InterfacesAccess Functionality SettingsAdvanced Slave Modbus Settings Failsafe Timer Functionality UDP Functionality UDP Entry Temperature FunctionalityUDP Settings Default CelsiusAnalog I/O Analog ChannelsAnalog Monitoring Application A4D2Alarm Settings Default CurrentDigital I/O Monitoring ApplicationInput Mode 147 Default Sink Output ModeActive Signal Default ManualPulse Mode Inactive SignalRelay I/O Monitoring Application A4D2Relay151 Remote Host Digital I/O ExtensionFront Door Warehouse Perle Iolan ReceptionInput number 1 Byte Current Alarm State 1 Byte z 0 = Not in alarmMessage type 1 Byte Input TCP Port Enable I/OExtension Local connection HostsSimultaneously Communicate to the Primary Host Temperature I/O Industrial Freezers TemperatureDefault RTD Basic Analog Alarm Settings Alarm SettingsClear Advanced Analog Alarm SettingsClear Mode Trigger TypeUDP Broadcast Packet UDP Unicast FormatSection Channel Length EnabledAnalog Section Length Pin Serial Pin Signal SectionDigital/Relay Section Length ChannelModbus Serial Application Connected to the Network Modbus SlaveUDP Unicast Example Modbus Serial Application Connected to the Serial PortFunction Codes Modbus I/O AccessModbus TCP Application Coil/Register Descriptions Input Registers Serial Port Coil/Register DescriptionsA4/T4 Registers Data Model A1/T1 A2/T2 A3/T3 A4/T4 Holding RegistersData Model D1/R1 D2/R2 Coils A4D2/A4R2 RegistersData Model Pin Coils Serial Pin SignalsD4/D2R2 Registers Data Model D3/R1 D4/R2 CoilsPC running a Modbus Serial Application TruePort Power Digital OutputTruePort I/O TruePort/Modbus CombinationPC running Custom Application API TruePort API Over TruePort OnlyIntroduction Accessing I/O Data Via TruePortSetup Response Format Format of API CommandsGet Commands Command FormatSet Commands Example 2 Turn on the first and second relay on a D2R2 unit Successful Response FormatUnsuccessful Response Format Example 1 Turn on the first relay on a D2R2 unitSnmp Traps Error CodesSyslog Configuring the System ChapterAlerts Management Snmp Traps Tab Field Descriptions Field Description Default 1 secondCustom App/Plugin Login Tab Field Descriptions Bootup Files Tab Field Descriptions Filename WebManager WebManager. Default DisabledMessage of the Day Motd Tab Field Descriptions Tftp HostRetry Default 3 secondsTftp Tab Field Descriptions Controlling the I/O Channels Activate Output Manually activates the channel output Saving Configuration Files System Administration ChapterManaging Configuration Files Downloading Configuration Files Server Name Downloading Configuration Files to Multiple IOLANsReboot Server Specifying a Custom Factory Default Configuration Uploading Configuration FilesCalibrating Analog Input Resetting the Iolan to the Default ConfigurationDownloading Iolan Firmware Calibrating I/OCalibrating Current Calibrating VoltageCalibrating RTD Calibrating Temperature InputCalibrating Thermocouple Calibrating Analog Channels Resetting Calibration DataResetting the Iolan to Factory Defaults Setting the IOLAN’s Date and TimeRebooting the Iolan Loading a Supplied Language Language SupportTranslation Guidance Software Upgrades and Language FilesCreating Terminal Definition Files Downloading Terminal DefinitionsFor example Resetting Configuration ParametersLost admin Password Virtual Modem Initialization Commands CommandsAT&Cn AT&SnAT&Rn DB25 Male Pinouts and Cabling DiagramsSerial Pinouts DB25 Female RJ45 DB9 Male I/O DB9 Male Serial OnlyDB25 Female EIA-232 Cabling DiagramsTerminal DB25 Connector DB25 Male10-pin Pin RJ45DB9 Male Iolan RJ45 DCE Modem DB25 ConnectorRxD TxD DTR 20 DTR GND Iolan DB25 Male/Female Setting JumpersPort Iolan Iolan RJ45 DIP Digital I/O Module Analog Input Module Digital Input Dry Contact Wiring I/O DiagramsDigital Input Wet Contact Digital Output Source Digital Output SinkVoltage Temperature InputAnalog Input CurrentRelay Output RTD 2-WireRTD 3-Wire RTD 4-WireNormally Closed Contact TruePort TruePort UtilityAPI Response Format API I/O Access Over TruePortAPI Request Format Error Codes Starter Kit Adapters/Cable AccessoriesRJ45F to DB25M DTE Crossover Adapter RJ45F to DB25M DCE Modem Adapter RJ45F to DB25F DTE Crossover Adapter RJ45F to DB9M DTE Crossover Adapter RJ45F to DB9F DTE Crossover Adapter Sun/Cisco RJ45M Connector Cable for Rack Mount ModelsStarter Kit Adapters/Cable Accessories Power/Ready LED continues to blink green in desktop models TroubleshootingHardware Problems Communication IssuesLogin Problems DeviceManager ProblemsHost Problems Login Problems Unknown IP Address Problems with TerminalsModels DHCP/BOOTP ProblemsLanguage Problems Long Reboot CycleIPv6 Issues Making a Technical Support Query Contacting Technical SupportFeedback on this Manual Repair ProcedureTCP Socket Profile Data LoggingTrueport Profile Line format for one UID is Modbus Remapping FeatureConfiguring the Modbus UID Translation Feature Create a configuration fileConfiguring the Modbus UID Translation Feature Glossary Silent Connection RIP RoutingInformation Protocol Roaming CallbackIndex BootpSnmp
Related manuals
Manual 224 pages 30.96 Kb Manual 88 pages 61.31 Kb Manual 122 pages 55.83 Kb

DS1, TS2 specifications

Perle Systems TS2 and DS1 are advanced serial-to-Ethernet devices designed to facilitate seamless integration of serial devices with modern IP networks. These devices serve as crucial tools for businesses looking to enhance their communication capabilities while leveraging existing infrastructure.

One of the standout features of the Perle TS2 and DS1 is their ability to support multiple serial protocols including RS232, RS422, and RS485. This versatile support allows businesses to connect various legacy devices to their networks, ensuring that critical equipment can still communicate effectively in an increasingly digital landscape.

The TS2 model is particularly noted for its dual serial ports, enabling simultaneous communication with multiple devices. This capability is invaluable for applications requiring real-time data transmission, such as remote monitoring and automated control systems. The DS1 model, on the other hand, is designed for single-port use, making it an ideal solution for smaller-scale operations or specific single-device connections.

Both the TS2 and DS1 incorporate advanced features such as configuration through a web interface, which simplifies setup and management. Users can easily access device settings and monitor performance metrics remotely, enhancing operational efficiency. These devices also support various network protocols such as TCP/IP, UDP, and ICMP, ensuring compatibility with a wide range of network architectures.

In terms of security, Perle Systems prioritize user data protection. The TS2 and DS1 offer features including SSL encryption and SSH protection, providing an added layer of security for sensitive information transmitted over the network. This is particularly important for industries where data integrity and security are paramount, such as healthcare and finance.

Additionally, the rugged design of both devices ensures reliable performance even in harsh environments. With extended temperature ratings and robust housing, the TS2 and DS1 can operate in diverse conditions without compromising functionality.

To summarize, the Perle Systems TS2 and DS1 provide a reliable and flexible solution for connecting legacy serial devices to modern networks. With their support for multiple serial protocols, web-based management, robust security features, and rugged design, these devices cater to a variety of industries looking to modernize their communication infrastructure while maintaining existing equipment. Whether for large-scale operations or smaller implementations, the TS2 and DS1 equip businesses with the tools needed for effective serial communication in an IP-driven world.