RATE

DPS3000 series tracks the rate of process change/minute for each channel. This rate is displayed by first pushing the CH. SEL key to select the channel whose rate is desired. Once the channel has been selected, push rate key. The display will briefly read 'cx-rate' (x=channel #), and then the monitored rate for that channel.

LIMITS

DPS3000 series units support limit alarms on all the channels. These limits can be programmed over the entire range of selected thermocouple or scale. Thus, not only can these units be used as monitors but they can also provide control capability on each channel. Limit values are programmed during CH Setup. Also programmed during CH Setup is the dead-band (hysteresis) value. This keeps the relays from chattering when the process is hovering just around the limit.

OUTPUTS

DPS3000 Series units can be ordered with either open collector outputs or electro-mechanical relays. Check model number printed on the unit.

Open Collector Option

Whenever a limit is reached an open collector output provides a 5 Vdc signal at 50ma. on the output connector, eg.. Limit #4 provides its 5 volt output signal between pins 7 & 8 of the card edge.

Figure 1. Open Collector Hookup Example

+5VDC

Instrument

7

8

+ OUTPUT

LOAD

- OUTPUT

Solid Sate Relay

LED, Buzzer, ETC.

Electro-Mechanical Relay Option

These relays are programmed during CH Setup to operate as either Normally Open (NO) or Normally Closed (NC). The default setting is Normally Open. Each of these limit relays provides a switched output whenever a limit is reached. The maximum rating for a 120Vac unit is 120Vac @ 0.5 amp or 28 Vdc @ 1.0 amp. A 240Vac unit is rated at 240Vac @ 0.25 amp. or 28Vdc @ 1.0 amp.

Figure 2. Electro-mechanical Relays Hookup Example

 

 

Instrument

 

PLUG-IN CONNECTOR

 

Limit # 4

7

 

 

Switched Output

 

8

120 VAC @ 0.5 AMPS

Limit # 3

5

Switched Output

 

6

120 VAC @ 0.5 AMPS

 

3

Switched Output

Limit # 2

 

4

120 VAC @ 0.5 AMPS

 

 

1

 

 

 

Switched Output

Limit # 1

2

120 VAC @ 0.5 AMPS

 

 

LIMIT RELAYS

 

 

Page 20

 

 

 

Image 21
Contents DPS3100 & DPS3200 series Programmable Scanners Channel Configuration SetupSystem Configuration Display ModesTable of Contents Trouble ShootingError Messages and Solutions Mounting Manual File omga31320404 SpecificationsDescription DPS3100 & DPS DPS3200RTD How to Display Parameters Displaying ParametersTo Display Perform Following Steps Scan Mode Elapsed Time ModeMode Function Performed Display ModesHigh/Low Channel Mode Deviation ModeTypes of Deviation Displays Setup Difference ModeDPS3000 Series is CH Parameter List Calibration/Range settingDisplay Options Relay Latch/Non-latch Display TimeSetup for Voltage or Current Input Channel ConfigurationSetup For Offset Setup For Low ScaleSetup For Tare Setup For SetpointSetup For Limits Setup for Universal Relay Channel 1 RelaySetup For Deadband Setup For Relay Normally Open/ClosedSetup Examples Setup for Thermocouple/ Thermistor/ RTD InputsSystem Configuration Setup For Display OptionsSetup For Display Time Setup for Buzzer Setup For Relay Latch/Non-LatchSetup For Cold Junction Calibration Setup For Channel CalibrationVoltage Range Setup for millivolt inputs Thermocouple Calibration ProcedureCurrent Range Setup Correct Range SettingsPeaks Programming Flow ChartsSYS CH Enter PasscodeSelect Channel Channel DiffCH ‘X’ Setpoint CH1 RELAY/UNIVERSAL Relay Thermistor LO VoltageCH ‘X’ Limit Relay Deadband Relay NO/NC Engineering UnitLimits RateOutputs Open Collector OptionFIG- 3. Connections & Rear View of Instrument Power Pin # Signal Relay Output Open Collector Output Connector PIN AssignmentTrouble Shooting Error Messages and SolutionsFactory Channel settings Mounting Panel Cutout and mounting hole dimensionsWarranty Page