4.1 Explanation of Display Prompts (continued)
oUt HI : (out high) Sets the high setting for the
pUlscale : (pulse out scaling) This allows the unit to output a pulse for each least signifi cant total count divided by the selected divider. The pulse out can be divided by 1 (d 1), 10 (d 10), 100 (d 100), or turned off (off ). With the divider set at 1, the unit will give a pulse out for every increment of the LSD displayed.
Note: For maximum battery life, turn the pulse output off when pulse output is not used.
Selecting the proper pulse output divider may be needed so that the pulse output does not exceed the maximum rate of the pulse output. If the pulse output
pulses too quickly a fl ashing display will result. Pressing the “M” key will result in a display of an error mes- sage “E PULSE”. Press the “E” key to return to the run mode.
P uuidth : (pulse width) Sets the pulse width of the pulse output. Selections are: 0.5 (1Hz), 0.25 (2Hz),0.125 (4Hz) or 0.0625 (8Hz). This menu item is skipped if pUlscale is turned off.
loC Code : (lock code) Sets the 5 digit lock code to be entered when the unit prompts ent Code . This allows the user to gain access to the menu when the unit is locked. Press the ↑ key to increment each digit. Press the ← key
to step to the next digit to the left. Press the E key to enter the displayed code.
Record this number for later use!LOCK CODE:
loC UnIt : (lock unit) Sets the panel lock ON or OFF. Press the ↑ key to select On or OFF. Press the E key to enter the displayed selection.
7