Omega Speaker Systems DPS3301 Display Modes, How to Reset and Program Thermocouple Type or RTD

Page 6

How to Reset and Program Thermocouple Type (or RTD)

A DPS3301-TC that is calibrated for a J, K, T, or E type thermocouple or an RTD model may be programmed for a specific thermocouple, or RTD (385/392) type, by going into SETUP mode (Look under ‘SETUP’). Alternately, a thermocouple/RTD may be selected by turning On power to the unit while holding in the appropriate key (see Figure 1). This procedure also clears the memory and programs factory defalult values for limits, rate timebase etc. Therefore, after performing Power-up reset, various parameters such as limits, rate time base etc., must be re-programmed to a desired value. However, if done in SETUP mode, no programmed parameters such as limits, Timers etc. are erased from the memory. It is recommended that thermocouple (RTD) selection be done in SETUP. Power-up reset should be performed if it is suspected that program memory may have been corrupted due to power surge, noise on electrical lines etc.

FIGURE 1. Thermocouple/RTD Selection Keys

E t/c

K t/c, RTD392,

Thermistor

Memory Clear only

T t/c

J (R, S or B) t/c,

RTD385

KEY

Input Type Selected

HI/LO

J (R, S or B , RTD 385)

 

Thermistor

C/F

K (RTD 392)

ALARM

T

TIMER

E

RESET

Memory cleared – no

 

factory default values

.

programmed.

NOTE: All keys, except RESET, clear memory and program necessary factory default values. RESET key clears memory only and programs no default values. However, previous thermocouple type is retained.

DISPLAY MODES

The DPS3301 can be programmed to display in any one of the following modes:

Mode

Display

Description

PROCESS

PrOCESS

Displays process value.

SETPOINT DEVIATION

SP. DEVN

Displays setpoint deviaition.

INSTANTANEOUS RATE

In. rAtE

Displays Instantaneous rate value.

PROCESS HIGH

Pr. HIGH

Displays process’ highest reading

PROCESS LOW

Pr. LO

Displays process’ lowest reading

ELAPSED TIME

ELPSd. T

Displays elapsed time.

TIMER 1 COUNT DOWN

tr1. Cnt

Display Timer 1 count down value

TIMER 2 COUNT DOWN

tr1. Cnt

Display Timer 2 count down value

SCAN

SCAn

Scans through all the above parameters

 

 

Page 6

Image 6
Contents DPS3301 Series Wall-MountProgrammable Temperature Monitor Specifications Description Thermocouple or RTD Selection Timers Specifications AccuracyDescription Thermocouple or RTD SelectionHow to Reset and Program Thermocouple Type or RTD Display ModesDisplay Units C/F Retaining User Settings on Power DownDisplay Hold Feature Setpoint DeviationFlow Chart Program LimitsHow To Increase/Decrease Programmable Values Setup Setup ModeEntering and Exiting Setup Mode Passcode EntryDisplay Option Program Controller ModeDisplay Time Rate Time-BaseCold Junction adjustment Thermocouple CalibrationProcess Limits 1 thru ‘PROGRAM LIMITS’ ModeThermocouple type Selection Selection of Limit 3 as Process or Rate LimitConfigure Timing Mode Programming LimitSelection of Limit 4 as Process or Deviation Relay Deadband Timers 1Configuring Limits Normally Open/Normally Closed Relay Latching/non LatchingRate Alarm Setpoint Deviation AlarmAudio Alarm On/Off Resetting Rate AlarmProcess Alarms Timers Open Collector OptionTimer Modes Elapsed TimeHow to Reset High & Low Peak readings PowerSignal Connection High and LOW PeaksOutput Connector PIN Assignment Output Connector Pin AssignmentDPS3301 Series Terminal Compartment Direct Interface to Universal Relay Module Mounting Page Page M4300/0907