Liebert NXL installation manual Right Side View

Page 14
DETAIL B

Installation Drawings

Figure 2 Input/output conduit detail drawing, 400kVA Liebert NXL UPS

DC

OUTPUT

(2) 3" CONDUIT

(2) 3.5" CONDUIT

BYPASS

INPUT

(2) 3.5" CONDUIT

(2) 3" CONDUIT

INPUT

BYPASS

(2) 3" CONDUIT

(2) 3.5" CONDUIT

OUTPUT

DC

(2) 3.5" CONDUIT

(2) 3" CONDUIT

 

LOW VOLTAGE 1.5" CONDUIT

 

LOW VOLTAGE

 

LOW VOLTAGE

 

(14) 1" CONDUIT

 

TOP VIEW

BOTTOM VIEW

1.5" CONDUIT

 

 

 

DC POSITIVE DC NEGATIVE

SEE NOTE 6

O.56

(14) TYP

1.75

(44) .87

TYP (22)

 

 

 

 

 

76.8

 

BYPASS

 

 

 

(1950)

 

 

 

 

 

 

NEUTRAL

 

 

 

 

 

GROUND BUS

 

B

 

59.4

 

LOCATION

 

 

 

 

 

( 1509)

 

(TOP ENTRY)

 

 

 

 

 

52.9

 

 

 

 

 

 

 

 

 

 

(1343)

 

BYPASS INPUT

 

 

 

46.4

 

 

 

 

(1178)

 

 

 

 

 

 

 

 

 

 

40.4

 

RECTIFIER INPUT

 

D

 

(1026)

 

 

 

34.4

 

 

 

 

 

 

 

 

 

( 874)

 

OUTPUT

 

 

 

28.4

 

 

 

 

( 721)

 

INNER PANEL

 

 

 

 

 

 

 

REMOVED

 

 

 

21.9

 

FOR CLARITY

 

 

( 556)

A

GROUND BUS

 

 

 

 

(BOTTOM ENTRY)

 

C

 

 

 

OUTPUT

 

 

 

 

 

 

 

 

 

NEUTRAL

 

 

 

 

 

 

 

 

 

.0

FRONT

 

 

RIGHT SIDE VIEW

( 0 )

1.75

 

 

.87

( 44 )

(BOTTOM

 

 

TYP

ENTRY)

 

1.75

 

( 22)

 

 

 

 

 

.98 (25)

 

1.75

( 44 )

 

 

 

TYP

 

 

 

 

( 44 )

 

 

 

 

 

TYP

 

 

 

 

 

(TOP

.56

1.75

 

 

 

ENTRY)

( 44 )

 

 

 

O ( 14 )

 

1.10

 

 

TYP

TYP

 

(28)

 

 

 

 

DETAIL A

 

O

.56

 

DETAIL C

 

( 14 )

 

TYP

56.4

(1432)

49.4

(1255)

43.4

(1102)

37.4

(950)

31.4

(797)

25.4

(645)

NOTES:

1.ALL DIMENSIONS ARE IN inches (mm).

2.24" MINIMUM CLEARANCE ABOVE UNIT REQUIRED FOR AIR EXHAUST.

3.KEEP CABINET WITHIN 15 DEGREES OF VERTICAL.

4.TOP AND BOTTOM CABLE ENTRY AVAILABLE THROUGH REMOVABLE ACCESS PLATES. REMOVE, PUNCH TO SUIT CONDUIT SIZE AND REPLACE.

5.UNIT BOTTOM IS STRUCTURALLY ADEQUATE FOR FORKLIFT HANDLING.

6.THESE BRACKETS CAN BE REMOVED DURING INSTALLATION BUT MUST BE REPLACED AFTER INSTALLATION.

7.CONTROL WIRING AND POWER WIRING MUST BE RUN IN SEPARATE CONDUITS.

8.ALUMINUM AND COPPER-CLAD ALUMINUM CABLES ARE NOT RECOMMENDED.

9.ALL WIRING IS TO BE IN ACCORDANCE WITH NATIONAL AND LOCAL ELECTRICAL CODES.

1.75 ( 44 )

TYP (BOTTOM ENTRY)

.88 X .56 SLOT

6PLACES EACH BAR

DETAIL D

1.75 ( 44 )

TYP

(TOP

ENTRY)

O.56 ( 14 )

TYP

10

Image 14
Contents Liebert NXL Ship-Ahead Input/Output Cabinet Product Warranty Registration Contacting Liebert for SupportFigures Page Important Safety Instructions Mechanical Installation UPS RoomClearances Floor Installation/AnchoringMoving the Cabinets Electrical Installation Dual InputPower Cable Connection Procedure Equipment Ground Current ratings-output Current ratings-rectifier inputCurrent ratings-bypass input Current ratings-battery Recommended conduit and cable sizesRecommended lug sizes Series Cable Size One Hole Two HoleInstallation Drawings TOP ViewRight Side View Front View Side View Front View Floor Mounts Installation Drawings Page Ti n Ne tIti That