Liebert NXL installation manual Moving the Cabinets, Clearances, Floor Installation/Anchoring

Page 7

Mechanical Installation

1.4.1Moving the Cabinets

The Liebert NXL Input/Output Cabinet can be handled with a forklift or similar equipment.

When moving the unit by forklift, care must be taken to protect the panels. Do not exceed a 15-degree tilt with the forklift. Bottom structure will support the unit only if the forks are completely beneath the unit.

Handling the cabinet with straps is not authorized.

1.4.2Clearances

Clearance around the front of the equipment should be sufficient to enable free passage of personnel with the doors fully open. Installation must leave a distance of 24" (610mm) between the top of the cabinet and any overhead obstacles to permit adequate circulation of air coming out of the unit.

Space must be reserved on the left side of the I/O cabinet. The UPS Rectifier/Inverter cabinet can be mounted only on the left side of the I/O cabinet.

1.4.3Floor Installation/Anchoring

If the equipment is to be located on a raised floor, it should be mounted on a pedestal designed to accept the equipment point loading. Refer to the base view to design this pedestal.

3

Image 7
Contents Liebert NXL Ship-Ahead Input/Output Cabinet Contacting Liebert for Support Product Warranty RegistrationFigures Page Important Safety Instructions UPS Room Mechanical InstallationMoving the Cabinets Floor Installation/AnchoringClearances Dual Input Electrical InstallationPower Cable Connection Procedure Equipment Ground Current ratings-bypass input Current ratings-rectifier inputCurrent ratings-output Recommended conduit and cable sizes Current ratings-batterySeries Cable Size One Hole Two Hole Recommended lug sizesTOP View Installation DrawingsRight Side View Front View Side View Front View Floor Mounts Installation Drawings Page That Ne tIti Ti n