Mechanical Installation
1.4.1Moving the Cabinets
The Liebert NXL Input/Output Cabinet can be handled with a forklift or similar equipment.
When moving the unit by forklift, care must be taken to protect the panels. Do not exceed a
Handling the cabinet with straps is not authorized.
1.4.2Clearances
Clearance around the front of the equipment should be sufficient to enable free passage of personnel with the doors fully open. Installation must leave a distance of 24" (610mm) between the top of the cabinet and any overhead obstacles to permit adequate circulation of air coming out of the unit.
Space must be reserved on the left side of the I/O cabinet. The UPS Rectifier/Inverter cabinet can be mounted only on the left side of the I/O cabinet.
1.4.3Floor Installation/Anchoring
If the equipment is to be located on a raised floor, it should be mounted on a pedestal designed to accept the equipment point loading. Refer to the base view to design this pedestal.