Liebert NXL installation manual Electrical Installation, Dual Input

Page 8

Electrical Installation

2.0ELECTRICAL INSTALLATION

This chapter provides guidelines for qualified installers who must have knowledge of local wiring practices pertaining to the equipment to be installed.

! WARNING

Risk of electrical shock. Can cause injury or death.

Check for voltage with both AC and DC voltmeters before working within the cabinet.

Only properly trained and qualified personnel wearing appropriate safety headgear, gloves, shoes and glasses should be involved in installing the cabinet or preparing the cabinet for installation.

2.1External Protective Devices

For safety, circuit breakers must be installed in the input AC supply and external battery system.

Given that every installation has its own characteristics, this section provides guidelines for qualified installation personnel with knowledge of operating practices, regulatory standards and the equip- ment to be installed.

External overcurrent protection must be provided. See Tables 1 through 4 for overload capacity.

Dual Input

When wiring the cabinet with a separate rectifier and bypass input, each input must be protected sep- arately.

Size the breakers according to the input currents shown in Tables 1 and 2.

2.2Power Cables

The UPS will require both power and control cabling. All control cables, whether shielded or not, should be run separate from the power cables in metal conduits or metal ducts which are electrically bonded to the metalwork of the cabinets to which they are connected

The cable design must comply with the voltages and currents in Tables 1 through 4, follow local wir- ing practices and take into consideration the environmental conditions (temperature and physical support equipment and methods), room temperature and conditions of installation of the cable and system’s overload capacity.

For cable entry terminal, refer to Figure 1.

! WARNING

Risk of electrical shock. Can cause injury or death.

Before cabling the UPS, ensure that you are aware of the location and operation of the external isolators that connect the input/bypass supply to the power distribution panel.

Check that these supplies are electrically isolated, and post any necessary warning signs to prevent their inadvertent operation.

NOTICE

For dual input operation, ensure that any busbars between the bypass and the rectifier input are removed.

When sizing battery cables, a maximum volt drop of 2VDC is permissible at the current ratings given in Table 4.

4

Image 8
Contents Liebert NXL Ship-Ahead Input/Output Cabinet Product Warranty Registration Contacting Liebert for SupportFigures Page Important Safety Instructions Mechanical Installation UPS RoomClearances Floor Installation/AnchoringMoving the Cabinets Electrical Installation Dual InputPower Cable Connection Procedure Equipment Ground Current ratings-output Current ratings-rectifier inputCurrent ratings-bypass input Current ratings-battery Recommended conduit and cable sizesRecommended lug sizes Series Cable Size One Hole Two HoleInstallation Drawings TOP ViewRight Side View Front View Side View Front View Floor Mounts Installation Drawings Page Ne t ItiTi n That