6.3BATTERY MODE OPERATION

Battery mode occurs in event of an extreme input voltage condition or com- plete utility failure. The battery system supplies power through the DC to DC converter to the inverter to generate power for the connected load.

AC INPUT BATTERY UPS ON BYPASS

Battery Mode Operation at 80-61%

During battery mode an alarm sounds every 10 seconds. This will change to two beeps every 5 seconds when the battery runs low (approximately 2 minutes remaining, but this is user configurable). The AC Input LED will extinguish, and the Battery LED will illumi- nate to warn that a utility problem has occurred. Each battery level indicator represents a 20% capacity level. As capacity decreases, fewer indicators remain illuminated. Refer to 10.0 - Troubleshooting.

For approximate battery run times, refer to 13.0 - Battery Run Times. The times listed in these tables are approximate based on resistive load and an ambient temperature of 77°F (25°C). To increase this time, turn off non-essential pieces of equipment (such as idle com- puters and monitors) or add the optional external battery cabinet.

! CAUTION

Turning OFF the UPS while in battery mode will result in loss of output power.

If the UPS is manually turned OFF, it must be manually restarted after utility power is restored.

If the UPS is turned OFF by a communication signal or because the batteries are depleted, it will operate as selected in the configuration program for Auto-Restart (see 8.1 - GXT 2U Configuration Pro- gram Abilities).

6.4BATTERY RECHARGE MODE

Once utility power is restored, the UPS resumes normal operation. At this time, the Battery Charger begins recharging.

18

Image 22
Contents Power Availability UPStation GXT 2UPage Table of Contents Tables Important Safety Instructions Page Glossary of Symbols Introduction Transient Voltage Surge Suppression Tvss EMI/RFI Filters RECTIFIER/POWER Factor Correction PFC CircuitMajor Components InverterDC to DC Converter Battery ChargerBattery Dynamic BypassGXT 2U Rear View Tower UPS Installation InstallationPreparation RACK-MOUNT UPS Conversion and Installation Bracket assembly into rack Prepare the UPS or battery Cabinet the equipment for UPS External Battery Cabinet Installation Controls and Indicators ON/ALARM SILENCE/MANUAL Battery Test ButtonBypass Indicator LED Amber LOAD/BATTERY Level Indicators 4 GREEN, 1 AmberFault Indicator LED RED Battery Indicator LED AmberAC Input Indicator LED Green Output Voltage SelectionBypass Mode Operation Normal Mode OperationOperating Instructions Battery Mode Operation Battery Recharge ModeCommunications Communications Interface PortPins 4 & 5 Remote Shutdown on Battery Auto-Enable Output Pin 6 Logic Pins 5 & 6 ANY-MODE ShutdownUPS Intelligent Communications Configuration Program GXT 2U Configuration Program AbilitiesMaintenance Battery ReplacementInternal Battery Replacement Procedures Fuse Replacement Troubleshooting AC LEDTroubleshooting guide Check load equipment for Your UPS has received a Alarm conditions Specifications Model RatingGXT2-1500RT120 GXT2-2000RT120 GXT2-3000RT120 Battery Cabinet Specifications Battery ParametersBattery RUN Times Product Warranty Registration Page Page Page Company Behind the Products