|
|
| Troubleshooting | |
Table 1 | Troubleshooting guide (continued) | |||
|
|
| ||
Problem | Cause | Solution | ||
|
|
|
| |
|
|
| Your UPS has received a | |
|
|
| signal or command from | |
|
|
| the attached computer. If | |
Fault and Bypass |
| this was inadvertent, | ||
| ensure the communication | |||
indicator LEDs | UPS shutdown due to a | |||
cable used is correct for | ||||
and diagnostic | command from the | |||
your system. For | ||||
LED C and E are | communications port(s). | |||
assistance, contact your | ||||
illuminated. |
|
| ||
|
| local dealer, Liebert | ||
|
|
| ||
|
|
| representative or the | |
|
|
| Liebert Worldwide Support | |
|
|
| Group. | |
|
| UPS detected a |
| |
|
| neutral reversal or a loss of |
| |
|
| proper grounding; |
| |
|
| continuous horn and UPS | Contact a qualified | |
AC LED is |
| will not start.This is active | ||
| only when power is first | electrician to verify site | ||
flashing. |
| |||
| applied to the input. Once | wiring. | ||
|
| |||
|
| the UPS is running, the AC |
| |
|
| LED will not start flashing, |
| |
|
| even if the input wiring is |
| |
|
| changed. |
| |
|
|
| Check battery connections, | |
|
|
| completely power down | |
|
|
| and restart UPS. | |
Battery LED is | Battery source is not | NOTE: If the battery circuit | ||
flashing. |
| available; continuous horn. | opens while the UPS is | |
|
|
| running, it will be detected | |
|
|
| when the next battery test | |
|
|
| is performed. | |
|
|
| The AC input powers the | |
|
|
| PFC input and serves as | |
|
|
| the bypass source. If the | |
|
| Bypass voltage is present, | AC is present but the | |
Bypass LED is | but is disabled for use | voltage or frequency | ||
because the voltage or | exceeds the acceptable | |||
flashing. |
| |||
| frequency is outside | range for safe operation | ||
|
| |||
|
| acceptable limits. | with a load, the bypass will | |
|
|
| be disabled and this LED | |
|
|
| will flash, indicating that the | |
|
|
| bypass is unavailable. |
30