Troubleshooting

Table 1

Troubleshooting guide (continued)

 

 

 

Problem

Cause

Solution

 

 

 

 

 

 

 

Your UPS has received a

 

 

 

signal or command from

 

 

 

the attached computer. If

Fault and Bypass

 

this was inadvertent,

 

ensure the communication

indicator LEDs

UPS shutdown due to a

cable used is correct for

and diagnostic

command from the

your system. For

LED C and E are

communications port(s).

assistance, contact your

illuminated.

 

 

 

 

local dealer, Liebert

 

 

 

 

 

 

representative or the

 

 

 

Liebert Worldwide Support

 

 

 

Group.

 

 

UPS detected a line-to-

 

 

 

neutral reversal or a loss of

 

 

 

proper grounding;

 

 

 

continuous horn and UPS

Contact a qualified

AC LED is

 

will not start.This is active

 

only when power is first

electrician to verify site

flashing.

 

 

applied to the input. Once

wiring.

 

 

 

 

the UPS is running, the AC

 

 

 

LED will not start flashing,

 

 

 

even if the input wiring is

 

 

 

changed.

 

 

 

 

Check battery connections,

 

 

 

completely power down

 

 

 

and restart UPS.

Battery LED is

Battery source is not

NOTE: If the battery circuit

flashing.

 

available; continuous horn.

opens while the UPS is

 

 

 

running, it will be detected

 

 

 

when the next battery test

 

 

 

is performed.

 

 

 

The AC input powers the

 

 

 

PFC input and serves as

 

 

 

the bypass source. If the

 

 

Bypass voltage is present,

AC is present but the

Bypass LED is

but is disabled for use

voltage or frequency

because the voltage or

exceeds the acceptable

flashing.

 

 

frequency is outside

range for safe operation

 

 

 

 

acceptable limits.

with a load, the bypass will

 

 

 

be disabled and this LED

 

 

 

will flash, indicating that the

 

 

 

bypass is unavailable.

30

Image 34
Contents Power Availability UPStation GXT 2UPage Table of Contents Tables Important Safety Instructions Page Glossary of Symbols Introduction Transient Voltage Surge Suppression Tvss EMI/RFI Filters RECTIFIER/POWER Factor Correction PFC CircuitMajor Components InverterDC to DC Converter Battery ChargerBattery Dynamic BypassGXT 2U Rear View Tower UPS Installation InstallationPreparation RACK-MOUNT UPS Conversion and Installation Bracket assembly into rack Prepare the UPS or battery Cabinet the equipment for UPS External Battery Cabinet Installation Controls and Indicators ON/ALARM SILENCE/MANUAL Battery Test ButtonBypass Indicator LED Amber LOAD/BATTERY Level Indicators 4 GREEN, 1 AmberFault Indicator LED RED Battery Indicator LED AmberAC Input Indicator LED Green Output Voltage SelectionBypass Mode Operation Normal Mode OperationOperating Instructions Battery Mode Operation Battery Recharge ModeCommunications Communications Interface PortPins 4 & 5 Remote Shutdown on Battery Auto-Enable Output Pin 6 Logic Pins 5 & 6 ANY-MODE ShutdownUPS Intelligent Communications Configuration Program GXT 2U Configuration Program AbilitiesMaintenance Battery ReplacementInternal Battery Replacement Procedures Fuse Replacement Troubleshooting AC LEDTroubleshooting guide Check load equipment for Your UPS has received a Alarm conditions Specifications Model RatingGXT2-1500RT120 GXT2-2000RT120 GXT2-3000RT120 Battery Cabinet Specifications Battery ParametersBattery RUN Times Product Warranty Registration Page Page Page Company Behind the Products