| Specifications | |
SPECIFICATIONS (CONTINUED) |
| ||||
|
|
|
| ||
Model Number |
|
|
| ||
Model Rating | 1500VA / 1050W | 2000VA / 1400W |
| 3000VA / 2100W | |
DIMENSIONS - in. (mm) |
|
|
|
| |
Unit | 3.5 x 21.5 x 17 | 3.5 x 21.5 x 17 |
| 3.5 x 24.2 x 17 | |
W x D x H | (87 x 547 x 430) | (87 x 547 x 430) |
| (87 x 618 x 430) | |
Shipping | 10.6 x 27.2 x 23 | 10.6 x 27.2 x 23 |
| 10.6 x 27.2 x 23 | |
W x D x H | (269 x 691 x 584) | (269 x 691 x 584) |
| (269 x 691 x 584) | |
WEIGHT - lb. (kg) |
|
|
|
| |
Unit | 50.6 (23) | 54 (24) |
| 69 (31) | |
Shipping | 59.5 (27) | 62.6 (28.4) |
| 78.0 (35.4) | |
INPUT AC PARAMETERS |
|
|
|
| |
Voltage Range (typical) | 120 VAC nominal; variable based on output load | ||||
100% - 90% loading | 90 VAC / 140 VAC | 90 VAC / 140 VAC |
| 90 VAC / 140 VAC | |
90% | 80 VAC / 140 VAC | 80 VAC / 140 VAC |
| 80 VAC / 140 VAC | |
70% | 70 VAC / 140 VAC | 70 VAC / 140 VAC |
| 70 VAC / 140 VAC | |
30% - 0% loading | 60 VAC / 140 VAC | 60 VAC / 140 VAC |
| 60 VAC / 140 VAC | |
Frequency | 40 - 70 Hz; Auto Sensing |
| |||
Input Power Cord | 10 ft. attached | 10 ft. attached |
| 10 ft. attached | |
w/ NEMA | w/ NEMA | w/ NEMA | |||
| |||||
OUTPUT AC PARAMETERS |
|
|
| ||
|
| (4) |
| (4) | |
Output Receptacles | (4) NEMA |
| (1) NEMA | ||
accepts 15A plug |
| ||||
|
|
| on 12 in cord | ||
|
|
|
| ||
Voltage | 100/110/115/120/127 | (user configurable) VAC; ±3% | |||
Frequency |
| 50 Hz or 60 Hz |
| ||
Waveform |
| Sinewave |
| ||
Main Mode Overload | 200% for 8 cycles; 130% for 10 seconds with transfer to bypass | ||||
BATTERY PARAMETERS |
|
|
|
| |
Type | |||||
Qty x V x Rating | 4 x 12V x 7.0 or 7.2 AH | 4 x 12V x 9.0 AH |
| 6 x 12V x 9.0 AH | |
Battery Mfg / Part # | China Storage Battery/ | Panasonic / | |||
CSB FR 1270 F2 | Yuasa / REW | ||||
| |||||
Backup Time | See 13.0 - Battery Run Times | ||||
Recharge Time | 5 hours to 95% capacity after full discharge into 100% load | ||||
ENVIRONMENTAL |
|
|
|
| |
Operating Temp | +32°F to +104°F (0°C to +40°C) | ||||
Storage Temp | +5°F to +122°F | ||||
Relative Humidity | 0% to 95%, | ||||
Operating Elevation | Up to 10,000 ft. (3000m) at 104°F (40°C) without derating | ||||
Storage Elevation | 50,000 ft. (15,000m) maximum | ||||
| <50 dBA, at 1 meter | <55 dBA, at 1 meter | |||
Audible Noise | from the rear | from the rear | |||
<45 dBA, at 1 meter | <50 dBA, at 1 meter | ||||
| |||||
| from the front or sides | from the front or sides | |||
AGENCY |
|
|
|
| |
Safety | UL 1778, | ||||
RFI/EMI | FCC Part 15, Subpart B, Class A | ||||
Surge Immunity | IEEE/ANSI C62.41 Category A & B | ||||
Transportation | ISTA Procedure 1A |
|