Liebert 208V, 2700VA user manual Battery RUN Times, Load % Estimated Time

Page 36

BATTERY RUN TIMES

 

Load %

Estimated Time

 

 

10%

91

 

20%

46

 

30%

30

Internal Battery

40%

21

50%

16

(minutes)

60%

11

 

70%

9

 

80%

8

 

90%

7

 

100%

5

 

10%

364

 

20%

184

 

30%

120

Internal Battery

40%

84

50%

64

+ 1 External Battery

60%

44

Cabinet (minutes)

70%

36

 

 

80%

32

 

90%

28

 

100%

20

 

10%

728

 

20%

368

 

30%

240

Internal Battery

40%

168

50%

128

+ 2 External Battery

60%

88

Cabinets (minutes)

70%

72

 

 

80%

64

 

90%

56

 

100%

40

 

10%

1092

 

20%

552

 

30%

360

Internal Battery

40%

252

50%

192

+ 3 External Battery

60%

132

Cabinets (minutes)

70%

108

 

 

80%

96

 

90%

84

 

100%

60

 

10%

1456

 

20%

736

 

30%

480

Internal Battery

40%

336

50%

256

+ 4 External Battery

60%

176

Cabinets (minutes)

70%

144

 

 

80%

128

 

90%

112

 

100%

80

Note: Approximate discharge times are in minutes and at 77°F (25°C) with a 100% resistive load.

32

Image 36
Contents UPStation GXT 2U Page Table of Contents Configuration Program Important Safety Instructions Page Glossary of Symbols Introduction RECTIFIER/POWER Factor Correction PFC Circuit Major ComponentsInverter Battery Charger BatteryDC to DC Converter Dynamic BypassGXT 2U Rear View Installation Tower UPS InstallationPreparation RACK-MOUNT UPS Conversion and Installation Page Prepare the UPS or battery cab Inet the equipment for rack UPS External Battery Cabinet Installation Controls and Indicators ON/Alarm Silence/Manual Battery Test ButtonLoad/Battery Level Indicators 4 Green, 1 Amber Fault Indicator LED RedBypass Indicator LED Amber UPS on Indicator LED GreenAC Input Indicator LED Green Output Voltage SelectionNormal Mode Operation Bypass Mode OperationBattery Mode Operation Operating InstructionsBattery Recharge Mode Pins 4 & 5 Remote Shutdown on Battery CommunicationsCommunications Interface Port Pins 5 & 6 ANY-MODE Shutdown Auto-Enable Output Pin 6 LogicUPS Intelligent Communications Configuration Program GXT 2U Configuration Program AbilitiesWhat You Will Need Maintenance Battery ReplacementInternal Battery Replacement Procedures Troubleshooting LED status Diagnosis/Audible alarmTroubleshooting Guide Problem Cause SolutionRoom ambient temperature That the bypass is Alarm Conditions Condition AlarmSpecifications Dimensions in. mmBattery Cabinet Specifications Dimensions in mmBattery RUN Times Load % Estimated TimeProduct Warranty Registration Page Page UPStation GXT 2U

208V, 2700VA specifications

The Liebert 2700VA, 208V is a robust and reliable uninterruptible power supply (UPS) designed to protect critical electronic equipment from power disturbances. This UPS is ideal for various applications, including data centers, telecommunications, and manufacturing environments, ensuring that business continuity is maintained even in the face of power outages or fluctuations.

One of the primary features of the Liebert 2700VA is its high power rating of 2700VA, which makes it suitable for supporting a range of devices, from servers to sensitive electronic equipment. With a nominal output voltage of 208V, it meets the electrical requirements of many industrial and commercial systems, making it an adaptable choice for enterprises with diverse power needs.

The Liebert 2700VA is equipped with advanced technologies that enhance its performance and efficiency. The unit employs double-conversion online technology, which ensures that the output power is consistently clean and stable. This technology continuously converts incoming AC power into DC and then back to AC, providing a seamless transition to battery power during an outage, eliminating any momentary interruptions.

In terms of characteristics, the Liebert 2700VA features an LCD display that provides real-time information on the UPS’s status, including input/output voltage, load level, and battery condition. This user-friendly interface allows for easy monitoring and management, making it convenient for IT professionals to maintain optimal operations.

Another significant aspect of the Liebert 2700VA is its advanced battery management system. This feature optimizes battery performance and life by regulating charging cycles and ensuring that batteries are in peak condition when needed. Furthermore, the UPS offers multiple communication options, including USB and serial connectivity, enabling integration with monitoring software and allowing for remote management capabilities.

The Liebert 2700VA also comes equipped with a range of protection features, including overload protection, short-circuit protection, and surge suppression. These attributes safeguard connected equipment from electrical anomalies, providing peace of mind in environments where downtime can be costly.

In conclusion, the Liebert 2700VA, 208V is a powerful UPS solution that combines advanced technology with essential features, making it a crucial asset for businesses seeking reliable power protection. Its robust capabilities, user-friendly interface, and extensive protection measures position it as an ideal choice for ensuring operational continuity in various critical applications.