GE Monogram ZTX Oil Pressure Sensor Input, Temperature Sensor Input, Fuel/Run Contact Output

Page 12

Engine Controller Accessory Board (Optional)

Oil Pressure Sensor Input

(Oil pressure contact to be normally open, held closed

by adequate oil pressure)

Approximately five seconds after emngine starter signal is sent, if terminal X3 is open to ground or returns to open state thereafter the generator Starter and Fuel/Run outputs are opened and locked out. After cause is deter- mined and corrective action is taken and verified by quali- fied technician, controller can be reset via reset button.

Temperature Sensor Input

(Temperature sensor contact to be normally open, closed by over-temperature condition)

Approximately five seconds after the engine starter signal is sent, if terminal X1 is connected to ground Starter and Fuel/Run outputs are opened and locked out. After cause is determined and corrective action is taken and verified by a qualified technician, the controller can be reset via the reset button.

Fuel/Run Contact Output

This output is activated closed whenever the engine is running. This will keep the fuel valve open as needed, and will cut fuel supply during the above mentioned lockouts or when the engine is no longer called to run.

Start Contact Output

This output is activated closed during cranking of the engine. Output will deactivate once the controller senses that the generator output has reached 33% of frequency indicating engine has reached running RPM.

Generator Battery Input

This input is required to support the controller’s operation.

Controller

 

 

 

 

 

 

 

 

 

Generator Battery Input￿

 

 

 

 

 

(12 Vdc)

Engine￿

 

 

X9

X10

 

 

+

–￿

Controller

 

 

+

–￿ +

–￿

 

 

X1

X2

X3

X4

X5

X6

 

 

 

 

 

Start Contact Output￿

 

 

 

 

 

(28 Vdc @ 5 amps)

Input￿

 

Input￿

 

Fuel/Run Contact Output￿

Temperature￿

Oil Pressure￿

 

(28 Vdc @ 5 amps)

Sensor￿

Sensor￿

 

 

(12 Vdc)

(12 Vdc)

 

 

10

ZTX Operation and Maintenance Manual (62R-2000)

GE Zenith Controls

Image 12
Contents GE Zenith Controls Authorized Service Table of ContentsIntroduction How to Remove the Cover Hazardous VoltageInstallation Hazardous VoltageInstallation cont’d Power ConnectionsControl Connections ControllerBattery and Holder Battery Harness MX50/90 Controller Functional Test Functional TestOptional Indicator LEDs RM4 Control Interface OptionalOptional Pushbuttons RM4 Control Interface Optional cont’d Automatic Generator Exerciser Selecting Exerciser Without TransferSelecting Exerciser With Transfer Temperature Sensor Input Generator Battery InputOil Pressure Sensor Input Fuel/Run Contact OutputExample Systems Partial Coverage SystemTypical Diagrams Troubleshooting Symptom Possible Cause Corrective ActionTroubleshooting cont’d Generator Fault Flash TablePage GE Zenith Controls