GE Monogram Zenith Controls, ZTX manual Troubleshooting, Symptom Possible Cause Corrective Action

Page 15

Troubleshooting

DANGER

HAZARDOUS VOLTAGE

(Can Cause Severe Injury or Death)

Turn OFF all power before installation, adjustment, or removal of transfer switch or any of its components.

Service must be performed by qualified personnel.

Symptom

Possible Cause

Corrective Action

 

 

 

 

P timer has not lapsed

See factory settings on Page 6

 

 

 

 

Generator control switch not in Auto

Refer to generator instruction manual

 

 

 

Generator will not start

Engine Start contact not wired

See Figure 3, Page 4

to generator

 

 

 

 

 

 

Starter battery is dead

Refer to generator instruction manual

 

 

 

 

No fuel

Refer to generator instruction manual

 

 

 

 

T timer has not lapsed

See factory settings on Page 6

 

 

 

 

Exercise in progress

See Page 9

 

 

 

Transfer switch does not

Utility breaker open or tripped

Clear fault and reset

 

 

transfer to Utility

 

Wait for utility to return to acceptable

 

Utility voltage out of range

 

level. See factory settings on Page 6.

 

 

 

 

 

 

Control harness unplugged

With all power disconnected,

 

reconnect harness

 

 

 

 

 

 

W timer has not lapsed

See factory settings on Page 6

 

 

 

 

Generator breaker open or tripped

Refer to generator instruction manual

Transfer switch does not

 

 

Generator voltage out of range

Refer to generator instruction manual

transfer to Generator

 

 

 

 

Control harness unplugged

With all power disconnected,

 

reconnect harness

 

 

 

 

 

 

U timer has not lapsed

See factory settings on Page 6

 

 

 

Generator will not stop

Exercise in progress

See page 9

 

 

 

 

Engine control switch in run position

Refer to generator instruction manual

 

 

 

 

Keypad cable unplugged

With all power disconnected,

 

reconnect harness

 

 

All LEDs off

 

 

Sources unavailable and/or source

Clear fault and reset breakers and/or

 

 

breakers tripped or open

check source availability

 

 

 

GE Zenith Controls

ZTX Operation and Maintenance Manual (62R-2000)

13

Image 15
Contents GE Zenith Controls Authorized Service Table of ContentsIntroduction Hazardous Voltage How to Remove the CoverHazardous Voltage InstallationPower Connections Installation cont’dController Control ConnectionsBattery and Holder Battery Harness MX50/90 Controller Functional Test Functional TestOptional Indicator LEDs RM4 Control Interface OptionalOptional Pushbuttons RM4 Control Interface Optional cont’d Automatic Generator Exerciser Selecting Exerciser Without TransferSelecting Exerciser With Transfer Fuel/Run Contact Output Temperature Sensor InputGenerator Battery Input Oil Pressure Sensor InputPartial Coverage System Example SystemsTypical Diagrams Symptom Possible Cause Corrective Action TroubleshootingGenerator Fault Flash Table Troubleshooting cont’dPage GE Zenith Controls