GE Power Supply user manual Communication, Description

Page 15

g

Digital EnergyGT Series

4 - Communication

4.1Description

The GT Series UPS is equipped with a communications interface, providing RS232 and dry contact protocols in one sub-D 9-pin female connector located at the rear of the unit. The communication port on the UPS can be connected to a computer. This port allows the computer to monitor the UPS status and control the operation of the UPS in some conditions. Using proper UPS management software and cable, the UPS can be managed in LAN/intranet/internet environments.

Some computers may have a special connector to link this communication port, or require a special plug-in card, or need a special UPS monitoring software. For specific information on GE Digital Energy connectivity products please contact your local dealer @ 1-800-637-1738.

The dry contacts (4.3) and (optional) SNMP plug-in card (4.4) can be connected at the same time. However, if both are operating simultaneously the remote shutdown facility for the dry contacts will not be available. Battery low and AC failure functions remain unaffected.

The pin assignment of the interface connector is defined as follows:

PIN

ASSIGNMENT DESCRIPTION

 

 

RS-232

Dry Contact

 

 

 

 

1

 

Low battery (Open collector)

 

 

 

2

UPS TxD (typical RS-232 level)

 

 

 

 

3

UPS RxD (typical RS-232 level)

Remote shutdown (5~12V)

 

 

 

4

Reserved for PNP

 

 

 

 

5

GND

GND

 

 

 

6

Reserved for PNP

Reserved

 

 

 

7

Reserved for PNP

Reserved

 

 

 

8

 

Utility Fail (Open collector)

 

 

 

9

 

 

 

 

 

Pin Assignment

Open Collector Circuit

The maximum voltage and current on pin 1,8 is 30VDC, 10mA.

OPM_GTU_19X_1K0_3K0_XUS_V014

14

GT-UL Series: User manual 1.2 (US)

Image 15
Contents Digital EnergyTMGT Series Digital Energy GT Series Important Safety Instructions Important Safety Instructions InstallationGeneral Transport/storage Batteries1kVA Model Fccis Interference StatementsRear panel InstallationPackage contents LocationMounting in a 19 enclosure Vertical installationConnecting the load Connecting an external battery packUL 1778 safety requirement Connecting the RS232/dry contact interfaceConnecting to the utility power supply 1000/1500VA Checking the site-wiring fault LED2200/3000VA Operation Panel OperationUse Normal Operation Start-upUse Abnormal Conditions Replace battery Bypass operationShort circuit Description CommunicationDry Contact RS232Specifications Snmp Plug-in Card optionalFunctions Maintenance Optional FeaturesRecycling the UPS at the end of service life Battery replacement procedure 1.5kVA 1 Remove front panelBattery replacement procedure 3kVA Problem Possible Cause Solution TroubleshootingGT Model 1000R UL 1500R UL 2200R UL 3000R UL Specifications