g
GE Digital Energy
| 8 | - Specifications |
| |
NetPro 19” model | : | 600 | 1000 | 1500 |
Ratings | : | 600 | 1000 | 1500 |
Voltage Amperes (VA) | ||||
with computer type load | : | 360 | 600 | 900 |
Watts (W) | ||||
with resistive load | : | 5 | 5 | 7 |
Input thermal circuit breaker (A) | ||||
Input fuse (A) | : | 8 | 8 | 10 |
Input converter | : | 220 - 240 V |
| |
AC input voltage |
| |||
AC input voltage range | : | 100% load: 187 - 264 V |
| |
|
| 70% load: 120 - 264 V |
| |
|
| input >264 Vac: UPS switches to battery operation | ||
Minimum | : | input >312 Vac: UPS shuts down, manual restart required | ||
187 V (at any load) |
| |||
Input current waveform | : | sinusoidal |
| |
Input current (A) at nom. inp. volt. | : | conform or better than EN | ||
2.0 | 3.3 | 5.0 | ||
Input power factor | : | 1 |
|
|
Input frequency range | : | 45 - 66 Hz |
| |
Inrush current | : | none |
|
|
Output converter | : | 230 V (suitable for 220 - 240 V loads) | ||
AC output voltage | ||||
AC output voltage tolerance | : | ± 2% |
|
|
Output frequency | : | 50 or 60 Hz, front selectable |
| |
Output frequency range | : | nominal ± 0.15% unless synchronized to the mains | ||
Output waveform | : | sine wave |
| |
Harmonic distortion | : | < 2% (typical 1.5%) with linear load | ||
Power factor | : | 0.6 (0.7 at 90% load) |
| |
Crest factor (peak to RMS current) | : | suitable for loads with c.f. up to 6:1 |
| |
Capacity appliance outlets | : | max. 10 A per outlet |
| |
Bypass | : | 195 - 264 V |
| |
AC input voltage range |
| |||
Frequency tracking rate | : | 2 Hz/sec. |
|
|
Frequency tracking range | : | nominal ± 10% |
| |
Phase difference | : | < 7º |
|
|
Typical transfer time, msec | : | 4 |
|
|
Overload capability | : | Fully protected against overload and short circuits | ||
Overload behaviour (battery operation) | : | 110% during 5 minutes; 150% during 5 seconds | ||
Overload behaviour during | : | depends on rating of thermal circuit breaker | ||
bypass operation |
| typical: | 125% of TCB value for 200 seconds | |
|
|
| 200% of TCB value for 10 seconds | |
|
|
| 300% of TCB value for 4 seconds | |
Batteries (ratings given for 25ºC) | : | 24 | 36 | 48 |
Nominal voltage (Vdc) | ||||
Number of 7 Ah batteries | : | 2 | 3 | 4 |
Type | : | sealed lead acid, maintenance free | ||
Service life | : | up to 6 years (depending on use) |
| |
Recharge current | : | 1.5 A |
|
|
Battery recharge time | : | 1.5 hours for 90% capacity, std battery | ||
(batt. discharged at 100% load) | ||||
Runtime in minutes | : | 12 | 12 | 10 |
at typical load (75%) | ||||
VA/Watts | : | 64 | 104 | 124 |
100/60 | ||||
200/120 | : | 34 | 54 | 71 |
400/240 | : | 15 | 27 | 36 |
600/360 | : | 9 | 15 | 24 |
1000/600 | : | - | 9 | 12 |
1500/900 | : | - | - | 6 |
General | : | 14 | 14 | 14 |
Weight without battery drawer (kg) | ||||
Weight with battery drawer (kg) | : | 19 | 22 | 24 |
Dimensions (hxwxd, mm) | : | 133.5 (3HU) x 450 (19”) x 440 |
| |
Depth required in 19” rack (mm) | : | 420 (without connectors) |
| |
Enclosure / protection | : | steel - plastic / IP20 |
| |
Environment | : | EN |
| |
Safety |
| |||
Electromagnetic compatibility | : | EN |
| |
Ambient temperature | : |
| ||
Audible noise at 1 meter | : | < 45 dB(A), load and temperature dependent | ||
Max. relative humidity | : | 95% |
| |
|
|
|
| |
OPM_NPE_19X_600_1K5_2GB_V030 |
| 13 | GE DE NetPro 19” |