GE 600 - 1500 VA manual Specifications, NetPro 19 model 600 1000 1500 Ratings

Page 14

g

GE Digital Energy

 

8

- Specifications

 

NetPro 19” model

:

600

1000

1500

Ratings

:

600

1000

1500

Voltage Amperes (VA)

with computer type load

:

360

600

900

Watts (W)

with resistive load

:

5

5

7

Input thermal circuit breaker (A)

Input fuse (A)

:

8

8

10

Input converter

:

220 - 240 V

 

AC input voltage

 

AC input voltage range

:

100% load: 187 - 264 V

 

 

 

70% load: 120 - 264 V

 

 

 

input >264 Vac: UPS switches to battery operation

Minimum start-up AC voltage

:

input >312 Vac: UPS shuts down, manual restart required

187 V (at any load)

 

Input current waveform

:

sinusoidal

 

Input current (A) at nom. inp. volt.

:

conform or better than EN 61000-3-2 (IEC 555-2)

2.0

3.3

5.0

Input power factor

:

1

 

 

Input frequency range

:

45 - 66 Hz

 

Inrush current

:

none

 

 

Output converter

:

230 V (suitable for 220 - 240 V loads)

AC output voltage

AC output voltage tolerance

:

± 2%

 

 

Output frequency

:

50 or 60 Hz, front selectable

 

Output frequency range

:

nominal ± 0.15% unless synchronized to the mains

Output waveform

:

sine wave

 

Harmonic distortion

:

< 2% (typical 1.5%) with linear load

Power factor

:

0.6 (0.7 at 90% load)

 

Crest factor (peak to RMS current)

:

suitable for loads with c.f. up to 6:1

 

Capacity appliance outlets

:

max. 10 A per outlet

 

Bypass

:

195 - 264 V

 

AC input voltage range

 

Frequency tracking rate

:

2 Hz/sec.

 

 

Frequency tracking range

:

nominal ± 10%

 

Phase difference

:

< 7º

 

 

Typical transfer time, msec

:

4

 

 

Overload capability

:

Fully protected against overload and short circuits

Overload behaviour (battery operation)

:

110% during 5 minutes; 150% during 5 seconds

Overload behaviour during

:

depends on rating of thermal circuit breaker

bypass operation

 

typical:

125% of TCB value for 200 seconds

 

 

 

200% of TCB value for 10 seconds

 

 

 

300% of TCB value for 4 seconds

Batteries (ratings given for 25ºC)

:

24

36

48

Nominal voltage (Vdc)

Number of 7 Ah batteries

:

2

3

4

Type

:

sealed lead acid, maintenance free

Service life

:

up to 6 years (depending on use)

 

Recharge current

:

1.5 A

 

 

Battery recharge time

:

1.5 hours for 90% capacity, std battery

(batt. discharged at 100% load)

Runtime in minutes

:

12

12

10

at typical load (75%)

VA/Watts

:

64

104

124

100/60

200/120

:

34

54

71

400/240

:

15

27

36

600/360

:

9

15

24

1000/600

:

-

9

12

1500/900

:

-

-

6

General

:

14

14

14

Weight without battery drawer (kg)

Weight with battery drawer (kg)

:

19

22

24

Dimensions (hxwxd, mm)

:

133.5 (3HU) x 450 (19”) x 440

 

Depth required in 19” rack (mm)

:

420 (without connectors)

 

Enclosure / protection

:

steel - plastic / IP20

 

Environment

:

EN 50091-1-1, EN 60950, IEC 950

 

Safety

 

Electromagnetic compatibility

:

EN 50091-2

 

Ambient temperature

:

-10 to +40ºC

 

Audible noise at 1 meter

:

< 45 dB(A), load and temperature dependent

Max. relative humidity

:

95% (non-condensing)

 

 

 

 

 

OPM_NPE_19X_600_1K5_2GB_V030

 

13

GE DE NetPro 19” 600-1500: User manual 3.0 (GB)

Image 14
Contents NetPro NetPro Installation IntroductionInstallation Procedure 1000VA model onlyUse Normal Operation OperationStart-up Use Status and Alarm Indications Runtime indication fig On line normal operation See On batteryBattery low end of runtime Programmed shutdown Use Setup ModeReplace battery Indicating LED is OffManual battery test Battery ManagementAutomatic battery test Relay Interface Card option CommunicationRS232 Port fig Snmp Interface Card optionOptional Features MaintenanceBattery replacement procedure Remove battery drawer. Be careful, heavy weightTroubleshooting Problem Possible Cause SolutionSpecifications NetPro 19 model 600 1000 1500 Ratings