2.2Installation Procedure

 

 

 

A

 

 

 

B

4

5

1

 

6

 

2

3

fig. 1

1.Remove the transport screws (A, fig. 1) and store them in the free holes (B, fig.1). Mount the NetPro 19” UPS in the 19” rack. The module must be supported by mounting rails, do not mount it by using the front brackets only. The front brackets allow mounting of handles (not included).

2.Make sure that the air vents in the side panels of the module are not blocked by the mounting rails or the side panels of the 19” rack.

2

7a

7

fig. 2

fig. 3

fig. 4

3.1000VA model only:

Battery extension module(s) can be installed to increase the battery runtime. Connect the DC connector of the battery module (7, fig. 2) to the DC socket of the UPS (2, fig. 1/2). You will hear a click when the cable is properly installed. Block the DC connector: install the small locking plate (7a, fig. 2) that came with the battery module, and fasten it with the screw provided. Using the DC connector of the battery module (not shown) you can install a second, third, etc. module. See also section 5.1.

4.Switch off your computer, and unplug it from the socket-outlet.

5.Disconnect the power cord from the computer (rating 250Vac/10A) and connect this cord to the mains input socket (5, fig. 1) of the UPS. See fig. 4.

6.Using the output cord(s) provided, connect the computer(s) to the appliance outlet(s) (1, fig. 1) of the UPS. Spread the loads over the appliance outlets as equally as possible. If you use a distribution box to connect more than one appliance per outlet, please note that the maximum AC-current rating of each appliance outlet is 10Amps. See fig. 3.

7.Connect the mains cord of the UPS to a working, grounded AC wall socket outlet. See fig. 4. The green LED 'on' (8, fig. 6) will blink now: mains power is available and the batteries are charging. If the LED does not blink but illuminates continuously instead, press ‘0’ for one second.

8.For best results, allow the UPS to recharge the batteries during a period of approx. 2 hours. It is acceptable to use the UPS without first charging the battery, but the runtime may be reduced.

9.For advanced communication possibilities, the RS232 interface port (6, fig. 1) can be connected to a computer system and/or optional interface cards (3, fig. 1) can be added. See chapter 4.

OPM_NPE_19X_600_1K5_2GB_V030

3

GE DE NetPro 19” 600-1500: User manual 3.0 (GB)

Image 4
Contents NetPro NetPro Installation IntroductionInstallation Procedure 1000VA model onlyStart-up OperationUse Normal Operation Use Status and Alarm Indications Battery low end of runtime On line normal operation See On batteryRuntime indication fig Use Setup Mode Replace batteryProgrammed shutdown Indicating LED is OffAutomatic battery test Battery ManagementManual battery test Communication RS232 Port figRelay Interface Card option Snmp Interface Card optionOptional Features MaintenanceBattery replacement procedure Remove battery drawer. Be careful, heavy weightTroubleshooting Problem Possible Cause SolutionSpecifications NetPro 19 model 600 1000 1500 Ratings