g

GE Digital Energy

3.3Use: Status and Alarm Indications

o

status indications

:

the operating mode

!

low priority alarms

:

abnormal operating situations

!!

high priority alarms

:

situations in which the actual

 

 

 

output voltage of the UPS is no

 

 

 

longer guaranteed; immediate

 

 

 

action should be taken

8

 

 

 

 

9

 

 

 

 

10

 

 

 

 

11

12

13

14

15

 

 

 

 

Indicators on front panel

 

 

 

 

on

alarm

on by-

progr.

repl.

on

buzzer*

 

 

pass

shutd.

batt.

batt.

 

Situation

 

 

 

 

 

 

 

 

 

 

 

o

Charger on (3.3.1)

- - - - -

 

fig. 6

 

 

 

 

 

 

 

 

 

 

 

 

o

Normal operation (3.3.2)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

!

On battery (3.3.3)

 

 

 

 

 

 

- - - - -

 

 

 

 

 

 

1x/8 s.

 

 

 

 

 

 

 

 

!!

Battery low (3.3.4)

 

- - - - -

 

 

 

 

- - - - -

 

 

 

 

 

1x/s.

 

 

 

 

 

 

 

 

!!

On bypass (3.3.5)

 

- - - - - - - - - -

 

 

 

- - - - -

 

 

 

 

1x/s.

 

 

 

 

 

 

 

 

!

Bypass out of limits

 

 

 

 

 

 

- - - - -

(3.3.6)

 

 

 

 

 

 

1x/8s.

 

 

 

 

 

 

 

!!

Overload (3.3.7)

 

- - - - -

 

 

 

 

- - - - -

 

 

 

 

 

1x/s.

 

 

 

 

 

 

 

 

!!

High temperature (3.3.8)

 

- - - - -

 

 

 

 

- - - - -

 

 

 

 

 

1x/s.

 

 

 

 

 

 

 

 

!Replace battery (3.3.9)

o

Progr. shutdown

- - - - -

- - - - -

1x/8s.

 

pending (3.3.10)

 

 

 

o

Progr. shutdown in

- - - - -

 

 

progress (3.3.10)

 

 

 

 

Operating modes and corresponding indications, see 3.3.1. – 3.3.10.

- - - - = intermitting

= continuous

*= resettable: press push button ‘I’ > 2 secs.

OPM_NPE_19X_600_1K5_2GB_V030

5

GE DE NetPro 19” 600-1500: User manual 3.0 (GB)

Image 6
Contents NetPro NetPro Installation IntroductionInstallation Procedure 1000VA model onlyOperation Start-upUse Normal Operation Use Status and Alarm Indications On line normal operation See On battery Battery low end of runtimeRuntime indication fig Programmed shutdown Use Setup ModeReplace battery Indicating LED is OffBattery Management Automatic battery testManual battery test Relay Interface Card option CommunicationRS232 Port fig Snmp Interface Card optionOptional Features MaintenanceBattery replacement procedure Remove battery drawer. Be careful, heavy weightTroubleshooting Problem Possible Cause SolutionSpecifications NetPro 19 model 600 1000 1500 Ratings