7 - Troubleshooting

Whenever a malfunction occurs, first check external factors (e.g connections, temperature, humidity or load) to determine whether the problem is caused by the unit itself or by its environment. Subsequently check the thermal circuit breaker: it may be tripped. If so: reset it (see 4, fig.1) and be sure that the UPS is not overloaded.

The following chart is a simple troubleshooting checklist only. If the suggested solution does not succeed, or if the information is insufficient to solve the problem, please contact your dealer or consult www.gedigitalenergy.com.

PROBLEM

POSSIBLE CAUSE

SOLUTION

Thermal Circuit Breaker (TCB)

UPS overload

Reduce load, reset TCB

tripped

 

(4, fig. 1)

 

 

 

 

System failure

Contact your dealer or consult

 

 

www. gedigitalenergy.com.

LED 'on bypass' blinks

Most probably an overload

See 3.3.7, reduce the load

 

 

 

 

Overtemperature

See 3.3.8

 

 

Allow the UPS to cool down

UPS will not switch on (without

Line cord not connected

Read 2.2

using 'battery start')

 

Connect line cord

and the output has been off for

 

 

Dead wall socket outlet, or

Contact qualified electrician

a few secs. (see also 3.2.5)

 

mains voltage out of limits

 

 

UPS overtemperature

See 3.3.8

 

 

Allow UPS to cool down

 

Tripped Thermal Circuit Breaker

See above

 

 

 

UPS will not switch on after

Batteries have been discharged

Contact your dealer or consult

installation, LED 'on' remains off

too deep during transport and/or

www. gedigitalenergy.com

 

storage

 

UPS switched off automatically

UPS overtemperature

See 3.3.8

 

 

Allow UPS to cool down

 

Mains failure, battery

Wait until mains returns

 

discharged

 

 

Programmed shutdown in

See 3.3.10

 

progress

 

 

UPS received shut down

Wait until mains returns

 

command from computer during

 

 

mains failure

 

 

The load is < 5% of the max.

Wait until mains returns

 

load and no mains power is

 

 

present.

 

 

(No-load shutdown function is

 

 

active, see 3.2.3)

 

LED ‘replace battery’

Battery test just after installation

Allow the UPS to recharge the

illuminates, buzzer is silent

or mains failure

batteries

 

Battery test shows weak battery

Read 6.2, replace batteries

 

 

 

 

 

 

OPM_NPE_19X_600_1K5_2GB_V030

12

GE DE NetPro 19” 600-1500: User manual 3.0 (GB)

Image 13
Contents NetPro NetPro Introduction Installation1000VA model only Installation ProcedureStart-up OperationUse Normal Operation Use Status and Alarm Indications Battery low end of runtime On line normal operation See On batteryRuntime indication fig Replace battery Use Setup ModeProgrammed shutdown Indicating LED is OffAutomatic battery test Battery ManagementManual battery test RS232 Port fig CommunicationRelay Interface Card option Snmp Interface Card optionMaintenance Optional FeaturesRemove battery drawer. Be careful, heavy weight Battery replacement procedureProblem Possible Cause Solution TroubleshootingNetPro 19 model 600 1000 1500 Ratings Specifications