GE LP 33 manual Switch OFF the inverter on each unit entering the screen, Inverter OFF

Page 46

6.In order to discharge the DC link capacitors, start once more the inverter on each unit through the screen:

MENU/COMMAND MENU/INVERTER ON

Remark: command INVERTER ON will be enabled only when the inverter voltage of each phase decreases below 7 VAC (about 30 seconds).

Before proceeding to step 7, check on the display panel that the DC link voltage (both polarities) Udcp and Udcn has reached the minimum voltage of 5 VDC (about 30 seconds).

7.Switch OFF the inverter on each unit entering the screen:

MENU/COMMAND MENU/INVERTER OFF

COMMAND MENU

INVERTER ON

*

INVERTER OFF

INVERTER: U1= 7V

U2= 7V U3= 7V

Frequency = 60.0Hz

Synchronized

Udcp= 5V

Udcn=

5V

Ubp=0V

Ubn=0V

O

Charge level

=

0%

 

Autonomy

=

0min

 

 

 

 

COMMAND MENU

 

INVERTER ON

 

INVERTER OFF

*

The load is now supplied directly from the mains through the manual switches Q2.

END OF PROCEDURE

WARNING !

The UPS cabinet contains parts electrically live.

Apart from the front door, do not open any other part of the UPS.

NOTE !

With separate mains inputs, it’s possible to disconnect mains rectifier.

Modifications reserved

Page 46/57

OPM_LPS_3UO_30K_40K_0US_V010.doc

Operating Manual LP 33 Series 30 & 40 kVA

Image 46
Contents LP 33 Series Manufactured byRevision Identification No Date of issue 01/01/2005 File nameModel Copyright 2005 by GE Consumer & IndustrialDear Customer Parallel version secured with RPA Table of contents Safety Rules Only ConditionGeneral Safety warnings Risk of electric shock PE Earth GND GroundIntroduction General DescriptionBlock Diagram and Main Elements Description DescriptionThrough the automatic bypass VFI Voltage Frequency Independent Mode operationOperation Modes Case of parallel systemMains recovery operation Automatic bypass operationMains failure operation Manual bypass operationWith redundant parallel system RPA Parallel System Parallel system for power capacityParallel system for redundancy UPS Paralleled on the Same Battery Pay attention to the following recommendationsService and Technical Support Riazzino CH Made in SwitzerlandRecycling AT the END of Service Life Layout Layout LP 33 Series / 30 & 40 kVASystem Handling Control PanelDo not switch on Q1 and Q2 with Command Push Buttons and SwitchesQ1 UPS output switch Q2 Manual bypass switch Total offLCD Screen Application on UPSSW Version 2ms 2ms 5ms 10msAlarms list 4130 Code Alarm Meaning4118 41404531 Code Alarm Meaning 45204530 4563Messages list 4500 Code Message Meaning 43624411 45214699 Code Message Meaning 46024603 4763Event report LP 33 Series LP 33 SeriesReset Total OFF Menu Screens MenuUser parameters screen Date and time setup = Day = MonthModem enabled = N Init=BEQV1X3&D0S0=2 Date and time set-upECO Mode Operation mode selection VFI Mode or ECO ModeECO Mode can only be activated on single units Telephone numbers set-upExample 3 ECO Mode during the night and week-end Example 2 ECO Mode Stop before ECO Mode StartD1 ÷ d7 Enabling time in function of weekdays ECO Start ECO Stop Start-up of the LP 33 Series Switch on the mains power at the input distribution panelOperation Executing Mainboard Self TestOperation mode selection Switch On the output switch Q1 PosSwitch On the inverter entering the screen Command MenuUPS shutdown with load transfer on manual bypass Q2 Switch OFF the inverter by entering the screenSwitch on the maintenance bypass Q2 Pos Enter must be pressed 2 timesInverter U1= Start-up following the operation on manual bypass Q2 Switch OFF the maintenance bypass Q2 PosSwitch on the inverter by entering the screen TestUdcp= Udcn= Ubp=0V Complete shutdownCharge level Autonomy 0min = 0% Restore to normal operation after total offRestore the command total off by entering the screen LED TestReset the UPS by entering the screen Restore to normal operation after EPO Emergency Power OffActivated Command Menu Inverter on Procedures for Parallel System LP 33 Series Parallel System start-up of the LP 33 Series40kVA P1 Switch on the output switch Q1 Pos. I on each unitUdcp=215V Udcn=215V Switch on the maintenance bypass Q2 I on each unit = 70% LP 33 40kVA P1Switch OFF the inverter on each unit entering the screen Switch on the inverter on each unit entering the screen Start-up following the operation on maintenance bypass Q2Open the maintenance bypass switch Q2 Pos on each unit Udcp=215V Udcn=215V Ubp=164V Ubn=164V FU1= Shutdown of a single unit in a parallel systemWith purpose to separate one unit from the parallel system U2= U3= Frequency = 60.0Hz Synchronized Udcp= Udcn= Ubp=0VStart-up an additional unit in a parallel system Switch on the output switch Q1 Pos. I on this unitSwitch on the inverter of this unit entering the screen Executing MainboardU2= U3= Frequency = Complete shutdown of a parallel systemSynchronized Udcp= Udcn= Ubp=0V Reset total off of the parallel system Booster, inverter eand Static-Switch shutdown40kVA P1 Reset all UPS by entering the screen Menu ComandiOptions Options General ViewCooling FAN Maintenance MaintenanceGeneral Maintenance Battery MaintenanceService Required Service RequiredDate Description Done by SitePro / Digital EnergyTM SG Series UPS

LP 33 specifications

The GE LP 33 is a cutting-edge locomotive designed and manufactured by General Electric for freight and transport companies. This model is renowned in the railway industry for its advanced technology, robustness, and efficiency. With a focus on enhancing performance while reducing environmental impact, the GE LP 33 stands out as a significant advancement in modern locomotive design.

One of the primary features of the GE LP 33 is its powerful engine, which offers impressive horsepower and torque. This allows the locomotive to pull heavy loads over long distances without compromising speed or efficiency. The engine is designed with fuel efficiency in mind, reducing operational costs for rail companies while also promoting sustainable practices.

In terms of technology, the GE LP 33 is equipped with sophisticated digital controls that streamline operations and improve reliability. The locomotive's onboard diagnostics system monitors performance in real time, allowing for proactive maintenance and reducing the risk of breakdowns. This not only ensures a smoother operation but also contributes to safety on the railways.

Another key characteristic of the GE LP 33 is its aerodynamic design. The streamlined shape minimizes air resistance, allowing the locomotive to achieve higher speeds with lower fuel consumption. This design philosophy extends to the overall build of the locomotive, which utilizes lightweight yet durable materials that enhance performance without sacrificing strength.

The GE LP 33 also incorporates advanced braking systems that increase safety and reliability. The autonomous braking technology enables the locomotive to respond rapidly to changing conditions, which is critical when transporting hazardous materials or operating in congested areas. Furthermore, the locomotive is engineered to meet strict environmental regulations, with reduced emissions and noise pollution compared to older models.

The GE LP 33’s flexible configuration options make it suitable for various applications within the freight industry. It can be customized to handle different types of cargo, from bulk materials to intermodal containers. This adaptability, combined with its powerful performance, makes the GE LP 33 a versatile choice for rail operators seeking to optimize their logistics.

In summary, the GE LP 33 represents a significant milestone in locomotive technology, focusing on performance, efficiency, and environmental responsibility. Its advanced features, robust design, and innovative systems position it as a leader in modern rail transport, catering to the evolving needs of the freight industry while paving the way for a more sustainable future in transportation.