Output Data Area Tab

The output data area describes data sent over the network by the Slave module to the PROFIBUS Master. These outputs are mapped, using the Output Data Area tab, from specific memory locations in the PLC where the Slave module resides.

Area

Read-only identifier for the row. Valid range: 1-32.

Type

Data type of area being defined. Valid types are Digital Out, Analog Out, and Empty. The default value is

 

Empty.

Size

Describes the size of the data area on the network. Set to 0 and read-only if Type is set to Empty. Valid

 

ranges:

If Type is set to Digital Out (Byte): 0—244

If Type is set to Analog Out (Word): 0—122

Note: The total number of output bytes for all entries cannot exceed 244.

Units

This read-only field gives the units for the Type specified.

 

If Type is set to Empty or Digital Out: Byte

 

If Type is set to Analog Out: Word

Ref

Location in PLC memory where the data to be sent is mapped. This field is read-only if Size is set to 0.

Address

This is a produced range and can be any range in %AI, %I, %Q, %G, %AQ, %R, %T, or %M. If Type is

 

Digital Out and the number of bytes (Size) is odd, an address in discrete memory must be used: %I, %Q,

 

%G, %M, or %T. Overlaps with another produced range are not considered fatal and can be included in a

 

valid configuration.

 

Default: For Digital Out, next available address in %Q

 

For Analog Out, next available address in %AQ

Length

The length of the reference mapped to the area.

Allowable ranges:For discrete memories: 0, 8, 16 ... X For register memories: 0, 1, 2 ... X

where X is the required length to hold the entire data area. The default value is the space required to map bytes specified by the entries in Type and Size.

Note: If an output data area is defined (Type and Size are specified) but Length is set to 0, a value of 0 is sent to the Master for that data area.

Power Consumption Tab

The information in this tab is read-only. It displays the power consumed by the module from the PLC backplane.

3-4

Series 90™-30 PROFIBUS Slave Module User's Manual – August 2004

GFK-2193A

Image 17
Contents Programmable Control Products GE Fanuc AutomationCimstar As Used in this PublicationContents Contents Related Publications Overview and SpecificationsProfibus Information Key IC693PBS201 Slave Module SpecificationsBus Communication Profibus BasicsProfibus Network Overview Amount of Data Transmission Duration Frequency Network TopologyPin No Signal Designation Network ConnectorsInstalling the Profibus Module in the PLC Rack InstallationReviewing System Power Requirements Baud Rate Line a Line B Glass Fiber Distance Max 1 Connecting the Slave to the Profibus NetworkNetwork Segment Length Network Termination Profibus Cable TypesRemoving the Module from the Rack Network Baud Rate Adding a Profibus Slave Module to the Hardware Configuration ConfigurationSettings Tab Configuring a Profibus Slave ModuleProfibus Slave Module’s Input Data Area Parameters Input Data Area TabOutput Data Area Tab Power Consumption TabColor Indication Status and DiagnosticsProfibus Slave Module LED Indicators Word 1 Slave Status Word Network Parameter ErrorsStatus/Firmware ID Array Commreq Ladder Instruction Communication RequestsSysid Examples Slot Word ValuePLC Operation of the Communications RequestCommreq Programming Requirements and Recommendations Error Detection and HandlingCorrective Actions for Commreq Errors Value Description Commreq Status WordProfibus Slave Module Commreq Reference Get Slave Status Command Block Basic ExampleGet Slave Status Commreq Memory TypesBit Meaning Value Get Slave Status Reply Data FormatNetwork Parameter Errors Value Type Dec Hex Description Read Module Header Command Block Basic ExampleRead Module Header Read Module Header Reply Data Format for Slave Clear Counters Reply Data Format Clear Counters Command Block Basic ExampleClear Counters Index