SUP Series™ UPS | 700VA & 1kVA |
Model Number
Nominal VA
700 | 1000 |
Electrical Input
Nominal AC Voltage | 120V or 230V |
| 120V or 230V |
7 (120V), 3.6 (230V) |
| 10 (120V), 5.2 ( 230V) | |
AC Voltage Window |
| ||
Frequency |
| 50/60 Hz (Auto – Tracking) | |
Frequency Range |
| 47 – 63Hz |
UPS is designed for use on 120V domestic or 230V international utility power with neutral, line and ground connections.
Electrical Output
Watts |
| 490 |
| 650 |
Nominal AC Voltage | 120V |
| 120V | |
Frequency |
| 50/60 Hz (Auto | ||
| ± 8% | |||
On Battery Voltage Regulation | ± 8% Typical (prior to low battery warning) | |||
Waveform |
|
| True Sinewave | |
Surge Protection |
|
| 125 Joules MOV | |
Unit Protection |
| Short Circuit, Overload & Over Temperature | ||
Efficiency AC to AC (Typical) | 97% (120Vac Input), 90% (230Vac Input) | |||
Battery |
|
|
|
|
DC Voltage |
| 24V |
| 24V |
Type |
| 12V, 7AH x 2 |
| 12V, 9AH x 2 |
|
| Lead Acid |
| Lead Acid |
Back Up Time | @ Full Load | 5 Minutes |
| 4.5 Minutes |
| @ 1/2 Load | 12 Minutes |
| 11 Minutes |
Recharge Time |
|
| 5 Hours | to 90% |
Battery times are approximate. |
|
|
|
Transfer Time
Bypass to Inverter
Inverter to Bypass
0ms
Electrical Connections
Input |
|
| 1 - 6’ Cord with |
| 1 - 6’ Cord with 5 |
|
|
| 1 – 6’ Cord with Schuko |
| 1 – 6’ Cord with Schuko |
Output |
|
| (3) |
| (3) |
Environmental |
|
|
|
|
|
Operating Temperature |
| 0º C - 40º C (32º F to 104º F) | |||
Altitude |
|
| 7,000 Feet |
| |
Humidity |
|
| 10% to 95% Non – Condensing | ||
Cooling |
|
| Low Velocity Forced Air Fans | ||
Audible Noise @ 1 meter | < 45dBA |
| |||
Controls and Indicators |
|
|
| ||
Control |
|
| One Main Control Button – UPS On/Off, Self Test, Reset & Silence Alarms | ||
Selection Control |
|
| Two LCD Metering Scroll Function Select Buttons | ||
LCD Display |
|
| AC Input Voltage, AC Output Voltage, Output Frequency, DC Battery Voltage, Internal UPS | ||
|
|
| Temperature, |
| |
|
|
| Timer – Minutes to Shutdown, Hours to Restart, Battery – Remaining Battery Time | ||
LCD Operational Symbols | Overload, Load Level, UPS is Loaded, Normal Mode, Buck Mode, Boost Mode, Timer Enabled, | ||||
|
|
| High Temperature, Fan Off, Alarm Off, UPS Fault, Battery Low, Battery Level | ||
Audible Alarms |
|
| Low Battery, Defective Battery, Low Battery, Overload, Over Temperature, AC Out of Range | ||
Communications |
|
| (Bundled UPSilon 2000 Software) | ||
Mechanical |
|
|
|
|
|
Dimensions H x W x D |
|
|
|
| |
Inches | (mm) | 7.9 x 7.1 x 14.2 | (200 x 180 x 360) | ||
Weight | lb. | (kg) | 33.1 (15) |
| 33.1 (15) |
Agency Listing |
|
| UL1778, CUL, | FCC Class A |
Note: The UPS will go to Green Mode whenever the output load is under 30 watts.
©2004 Falcon® Electric, Inc. All rights reserved. Falcon® and the Falcon Electric logo are registered trademarks of Falcon Electric, Inc. All other brand names and trademarks are the property of their respective owners.
The information and specifications stated in this document are subject to change without notice.
Falcon Electric, Inc. - 5106 Azusa Canyon Rd. - Irwindale, CA 91706 - 800.842.6940 Fax 626.962.7720