Eaton Electrical 1000 quick start Repeat for each Group B through P Schedule Groups, Grpa OFF

Page 4

C. Set Group Description

Use UP/DOWN to highlight the MODIFY DESCRIPTION option and hit SEL. The SELECT DESCRIPTION screen will be displayed:

SELECT DESCRIPTION

For Group A

None

Offices_____________

Hallways

Parking

Exterior

Signs

The list of predefined descriptions is several pages long. Use UP/ DOWN and SEL to scroll through the screens and choose a predefined description or choose enter characters (at the end of the list) to enter a custom description:

ENTER DESCRIPTION

_<

Use UP/DOWN to scroll up or down through the alphabet and SEL

to enter one letter at a time. Continue hitting SEL across to the right screen of the line to enter the description.

Hit BACK once (or twice for custom desciptions) to return to the CONFIGURE GROUP A screen.

D. Test Group

The group has now been configured and is ready to be tested. Verify that all breaker primary handles have been returned to the ON posi- tion. Hit BACK to return to the MAIN MENU:

MAIN MENU

Command

Groups ON/OFF

Panel Status Screen

Configure Groups

Configure Date/Time

Group

Status:

ON: ABC

N

OFF:

DEFGHIJKLM OP

Use UP/DOWN and SEL to select Command Groups ON/OFF. The COMMAND GROUPS screen will be shown:

COMMAND GROUPS

ON:

 

A

BC

 

N

OFF:

 

_

DEFGHIJKLM

OP

GRPA

 

 

ON

 

Cleaning

Lights

 

Use BACK/SEL to select

UP - ON, DOWN - OFF

Hold down BACK to exit

Use the BACK and SEL to highlight the desired group (in this case, A). Use UP to turn the group on and DOWN to turn the group off. Verify that the correct set of breakers is turned on and off with the group. If not, repeat Step 4A — Configure Breaker Group A — Associate Loads With the Group.

If there is an associated input for this group, turn the group off again with the COMMAND GROUPS screen above. Use the actual input — switch, motion detector, etc., to trip the input. Verify that the proper group is turned on. If not, repeat Step 4B — Configure Breaker Group A — Associate Inputs With the Group.

Verify that the group description on the fifth line of the COMMAND GROUPS screen is the correct description for this group. If not, repeat Step 4C — Configure Breaker Group A — Set Group Description.

5.Repeat Step 4 for each Group B through P

6.Schedule Groups

The final step in initial setup is to enter the schedules for each group. From the MAIN MENU, select Configure Groups. The following screen will be displayed:

SELECT

GROUP

 

 

 

TO

CONFIGURE:

 

 

 

 

 

 

 

Group A

 

GRPA

OFF

 

GROUP

A

LIGHTS

 

 

15

loads in group.

 

Use

up/down/sel to

 

change

selection

 

 

 

 

 

 

 

Hit SEL to select Group A. The following menu is displayed:

CONFIGURE GROUP A

Group A GRPA

ON

OFFICE LIGHTING

 

Associate Loads

 

Associate Inputs

 

 

 

Modify Schedules

 

Modify Description

 

 

Select Modify Schedules. The following screen is displayed:

MODIFY SCHEDULES FOR

Group A OFFICE LIGHT

Use SEL to edit sch.

Days

--ON-- --OFF-

(empty schedule)

Hit SEL to choose the empty schedule item. The following screen is displayed:

ENTER SCHEDULE DETAIL

For GROUP A

DAYS: _______

Start time: 12:00 AM

End time: 12:00 PM

Clear Schedule

Press BACK when done

4

EATON CORPORATION Cutler-HammerPow-R-Command 1000 LCD Display Instruction Leaflet IL01412010E Effective: June 2006

Image 4
Contents Pow-R-Command1000 LCD Display Quick Start Guide IntroductionLCD Programming Procedure LoginPress any key to begin. The Eaton logo will be displayed Set Date/Time/DST/LocationConfigure Group a Office LightingAssociate Loads Pick Group a LoadsRepeat for each Group B through P Schedule Groups Grpa OFFPick Schedule Days WeekdaysWeekends Clear All Days Pick specific days Yes No Smtwtfs Weekday 0930A 0530PPPRC1000 Programming Worksheets T W T F S